13
EGW05-SWHPEG-20140724
TM
TM
COLD SURFACE TEMPERATURE HUMIDITY RESET
The ECC control system includes a sensor that measures the temperature of the coldest surface in the pool enclosure,
usually an exterior window or door frame. When the temperature of this surface approaches the dewpoint temperature
of the space, the controller lowers the humidity setpoint to activate dehumidification. This function helps to prevent
condensation on the cold surface. Typical locations for this condensate prevention surface temperature sensor are north
facing exterior walls, windows, window/door frames and skylights.
SPACE HEATING
Space heating via heat recovery uses full proportional control of the space dry bulb temperature by staging compressor
loading of unit capacity with humidity override. Heat is recovered automatically from the pool room return air. The
PoolPak™ automatically controls the output of the optional factory-installed auxiliary air-heating coil which can be hot
water, steam, electric or gas.
NETWORKING MULTIPLE UNITS
ECC networking allows multiple units to be connected together. The units will work with each other to control water
temperature, air temperature and relative humidity. Networked units have all the features of standard units plus the ability
to control water temperature in multiple pools. All units on the network are accessible from a single remote interface
unit for convenience.
SMART ECONOMIZER (SR)
The Smart Economizer utilizes the simultaneous operation of the heat recovery and economizer control sequence.
When the PoolPak™ compressor is operating in the heating and/or dehumidifying heat recovery mode, return air passes
through the evaporator. The sensible and latent heat in the return air is transferred to the refrigerant. Air leaving the
evaporator is cold and saturated. The exact temperature and dew point of the air leaving the evaporator is monitored
and compared to outside air temperature and dew point. If the outside air is warmer and/or dryer than the air leaving
the evaporator, all the air leaving the evaporator is exhausted and 100% outside air is drawn into the PoolPak™. All the
heat recovered in the PoolPak™ unit refrigerant is transferred to the supply air in the air reheat condenser. The Smart
Economizer saves more energy than a standard mixing box and economizer.
SPACE COOLING (OPTIONAL)
If space cooling is required and the unit is equipped with an auxiliary refrigerant condenser (air-cooled or water-cooled),
the ECC will activate the space cooling mode of operation. In this mode, the heat removed from the space air will be
directed to the auxiliary condenser. The air cooling mode of operation is independent of the need for dehumidification.
The PoolPak™ SR and SEP units are equipped with economizer sections. The ECC will automatically select the most
economical method for space cooling. An economizer utilizes outside air rather than the refrigeration system to achieve
space cooling. A sensor connected to the ECC monitors the outside air temperature. When appropriate, the controller will
disable the compressor and bring in cool outside air for economical operation.
Air Conditioning with Air-Cooled Condenser
The PoolPak™ can be equipped with a properly sized remote air-cooled condenser. This remote condenser can be
“piggyback-mounted” on the PoolPak during installation or installed on a separate pad.