Section IV: Installation
Figure 4-10. Remote ACC Installation Around Walls or Obstructions
ALL_WallsorObstructions_20131111.eps
Multiple Units
For units placed side by side, the minimum distance between units is the width of the largest unit. If units are placed end
to end, the minimum distance between the units is 4 feet.
Figure 4-11. Remote ACC Installation When Installing Multiple Units
ALL_MultipleUnits_20131111.eps
Units in Pits
The top of the unit should be level with the top of the pit and side distances increased to “2W”. If the top of the units is
not level with the top of the pit, discharge cones or stacks must be used to raise discharge air to the top of the pit. This is
a minimum requirement.
Figure 4-12. Remote ACC Installation When Installing Units in Pits
ALL_UnitsinPits_20131111.eps
MIN.
W*
AIR FLOW
* W”=Total width of the condenser
MIN.
* W”=Total width of the condenser
”
W*
AIR FLOW
AIR FLOW
* W”=Total width of the condenser
”
MIN.
MIN.
AIR
FLOW
2W*
2W*
STACK
(BY OTHERS
IF SUPPLIED)
10’ MAX.