30
EGW06-PCPEG-20140813
TM
TM
Section IV: Installation
ECC-PCP CONTROLS FIELD WIRING
OVERVIEW
The ECC-PCP is the Electronic Control Center programmable controller designed specifically for the PoolComPak™
dehumidification system. It is a robust system capable of a variety of functions. The following text describes the field
wiring required for for proper operation of the ECC-PCP dehumidification system in a typical PoolComPak™ unit
installation.The field wiring diagram (
) shows the location of the connections for the sensors
and other required devices.The numbers following the text identify the location on the field wiring diagram where each
device is connected to the PoolComPak™ unit electrical panel.
REMOTE INTERFACE UNIT (1)
The remote interface unit allows the user to view space temperature, pool water temperature, and relative humidity,
change set points, and receive fault notifications. It should be mounted in a convenient location that is outside the pool
area. The ambient temperature of the mounting location must always be above 32 F.
NOTE
The maximum distance from the Remote Interface Unit to the PoolComPak™ unit is
1000 feet. For distances greater than 1000 feet, contact the factory.
The control panel does not contain any sensors and should be mounted outside the pool enclosure. A factory supplied 6 ft
cable RJ25 (6 conductor) must be installed between the PoolComPak™ unit and the control panel.
For distances greater than 6 feet, use 6 conductor, 22 AWG, shielded, twisted-pair cable along with the supplied RJ25
jack and second 6 foot cable shipped loose with the unit.
The wall mounting of the terminal first requires the back piece (A) of the RIU assembly. The RIU is designed to fit a
single gang, extra-deep electrical box mounted horizontally in the wall. The RJ25 jack and most of the black cable
should be placed inside the box before installing the mounting bracket. A ¾” hole must be drilled for the 6-conductor
cable which connects the remote interface unit to the PoolPak™ unit. The below is specific mounting instructions that
correspond to the mounting schematic below:
1.
Fasten the back piece (A) to the gang box using the rounded-head screws supplied in the packaging. Use the screws
that come with the box to secure the bracket.
2. Thread the 6-conductor cable through the back piece (A) and connect to the back of front panel (B).
3. Rest the front panel (B) on the back piece A and fasten the parts together using the flush-head screws supplied in the
packaging.
4. Finally, fit the click-on frame (C).
Figure 4-3. Remote Interface Mounting Plate
ALL_EG_RIUMounting_20131219.eps
A