15
EGW06-PCPEG-20140813
TM
TM
Section II: Principles, Functions, and Features
TECHNICAL SUMMARY
Table 2-1. RoofPak Technical Data
DIMENSIONAL DATA
Figure 2-2. PCP RoofPak Dimensions
PCP_EG_RoofpakDimensions_20131108.eps
ROOFPAK WEIGHTS
Table 2-2. RoofPak Weights
Model
Configuration
Weight (lbs)
AWH/HCDH 3500/4000
With Integral Gas or Electric Heat and With Remote ACC
2,900
AWH/HCDH 3500/4000
With Integral Gas or Electric Heat and With Integral ACC
3,700
AWH/HCDH 3500/4000
With No Integral Auxiliary Heat and With Integral ACC
2,700
RoofPak weights are also included with the RoofPak Generic Product Drawings found in the
section of the PoolPak™ website.
Model Number
AWH / HCDH 3500 - 10 Ton
AWH / HCDH 4000 - 12 Ton
Pool Size (Sq. Ft.)
1,200 - 2,000
1,400 - 2,500
Reheat Capacity (MBH)
170
200
Moisture Removal (Lb/Hr@82°F/60%RH)
63
70
Pool Water Flow (GPM)
26
28
Pool Water Condenser PD (FT WC)*
20
30
Pool Water Condenser Capacity (MBH)
170
200
Outside Air (CFM)(Nominal)
0 - 2,000
0 - 2,000
Total Supply Airflow CFM (Maximum)
3,500 - 7,000
4,000 - 7,000
Refrigerant Charge (lbs)
81
83
Dimensions (in inches) with integral air-cooled condenser and gas furnace
Length
264
264
Width
57.4
57.5
Height
52.5
52.2
OA
45.3
15.2
13.4
44.0
FRONT VIEW
52.5
SA
120.0 C.G.
* Side return air available; horizontal return air available without integral air-cooled condenser
LEFT VIEW
RA*
264.0