POM2-3333
Merger Unit Test User
Manual
46
3.9 Voltage Switch and parallel logic
3.9.1 Testing wiring connection
POM2-3333
MU
SV to MU: Analog signal,
IEC 60044-8, 9-2 (or 9-2LE)
SV from MU: 9-2 (or 9-2LE), IEC 60044-8
Switch position
:
GOOSE or binary
input/output
3.9.2 Test configuration:
It needs to guarantee that 2 groups of bus bar voltages of MU separately connect into the
output channel of tester, Va, Vb, Vc and Va’ Vb’ Vc’. The other configuration of Sampling
value could be set as per 3.1.2.
GOOSE Publish
In the following interface, insert SCD file and choose GOOSE control module which is
requested by voltage switch or voltage parallel to publish the GOOSE message.
The configuration of GOOSE, see appendix: parameter configuration of Message Publish.