POM2-3333
Merger Unit Test User
Manual
21
Composite error test
SN Item
Amplitude
Out.
Phase
Max.
error
Min.
error
Avg.
error
Con
1
Ia PROT 1
1000.000A
0.000°
2.79%
2.76%
2.78%
合格
2
Ia PROT 2
1000.000A
0.000°
2.84%
2.80%
2.82%
合格
3
Ia Meas
5000.000A
0.000°
0.47%
0.46%
0.47%
合格
4
Ib PROT 1
1000.000A
-120.000° 2.86%
2.73%
2.79%
合格
5
Ib PROT 2
1000.000A
-120.000° 2.84%
2.77%
2.81%
合格
6
Ib Meas
5000.000A
-120.000° 0.37%
0.36%
0.37%
合格
7
Ic PROT 1
1000.000A
120.000°
2.86%
2.77%
2.81%
合格
8
Ic PROT 2
1000.000A
120.000°
2.89%
2.82%
2.86%
合格
9
Ic Meas
5000.000A
120.000°
0.41%
0.39%
0.40%
合格
10
Va 1
127000.000V 0.000°
0.36%
0.34%
0.35%
合格
11
Va 2
127000.000V 0.000°
0.34%
0.33%
0.33%
合格
12
Vb 1
127000.000V -120.000° 0.34%
0.33%
0.33%
合格
13
Vb 2
127000.000V -120.000° 0.33%
0.32%
0.33%
合格
14
Vc 1
127000.000V 120.000°
0.35%
0.33%
0.34%
合格
15
Vc 2
127000.000V 120.000°
0.35%
0.33%
0.34%
合格
Note:
There are totally 22 channels in the sample MU. In this test, we only choose 15
channels to make test.
Absolute delay
Setting value
Max. value
Min. value
Avg.
2.4uS
2.3uS
2.3uS