POM2-3333
Merger Unit Test User
Manual
14
Step 1: Select the message receive type
IEC61850-9-2, IEC60044-8.
Select it according to the message output. Please note the wiring connection for
IEC61850-9-2 and IEC60044-8 is different from that in hardware. Please refer to the
hardware structure in part 2.1.
Step 2: Map the message channel
Press channel configuration to import SCD file by clicking “import SCD file” in the
below figure. The software will automatically match between MU output channel and
input control channel.