Caution:
Please be aware of the temperature surge risk when setting a
large temperature gap between TL--TS /TS--TH. Recommend to set
the gap smaller than 10 degrees. The tighter gap the more stable real
temperature.
Note:
Please check and test your setting every time before leaving
controller to a long-term running.
6.2
Temperature Alarm Setting (AL, AH)
When measured temperature ≤ AL, low
temperature alarm will be
triggered, buzzer will alarm until temperature
>
AL or any key is
pressed.
When measured temperature ≥ AH, high temperature alarm will be
triggered, buzzer will alarm until temperature
<
AH or any key is
pressed.
Note:
If you set the AL ≥ TL, then the real low temperature alarm
point is TL-
0.5℃
.
If you set the AH ≤ TH, the real high alarm point is
TH+0.5℃
.
6.3 Compressor Protection Time (PT)
Under cooling mode, compressor protection will keep the refrigeration
off between cycles to protect your compressor. That means
compressor won't start refrigeration immediately, but waiting for a
delay time if it falls into the PT time frame. Delay time will be