6.
Menu Instruction
Menu
Code
Function
Setting
Range
Default
Setting
Remarks
TL
Low Temperature Point
-40.0~99.9
℃
23.0℃
6.1
TS
Shutdown Temperature Point -40.0~99.9
℃
25.0℃
TH
High Temperature Point
-40.0~99.9
℃
27.0℃
AL
Low Alarm Temperature
-20.0~(TL-0.5)
℃
-3
0.0℃
6.2
AH
High Alarm Temperature
(TH+0.5)~
80.0℃
9
0.0℃
PT
Compressor Delay
0~10min
2min
6.3
CF
℃/℉ Display
℃/℉
℃
6.4
CA
Temperature Calibration
-20.0~
20.0℃
0
℃
6.5
6.1 Temperature Control Range Setting (TL, TS, TH)
This controller has a heating and cooling control outlets. However,
you can only use the heating or cooling side for your project.
When measured temperature ≤ TL
, system enter heating state, the
heating outlet relay starts to work; when it heats up to shutdown point
(TS), the heating relay stops.
W
hen measured temperature ≥ TH
, system enter cooling state, the
cooling outlet relay starts to work; when it cools to shutdown point
(TS), the cooling relay stops.
In case the time interval between two cooling action is less than PT,
please refer to
6.3
.