7
-
Typical Utility Closet And Dimensions
(FOR REFERENCE ONLY)
~2-1/4"
~1"
11-1/2"
10"
10"
duct
3"min.
3"
min.
Electrical connection
4" min.
Door/access panel
Thermostat
Connection
Unit
fron
t
Architectural Louver
UNIT INSTALLED THROUGH
FRONT OF CASE
Top View
A
B
A Minimum recommended access door width: 30"
B Minimum recommended access door height : 50"
Option 2
Return air grille
Inside wall
Option 1
Access panel
with return air grille
Rigid
ductwork
Flexible or
rigid duct
Air discharge
outlet
Unit
Wall
plenum
Wall plenum
divider
Drain fittings 3/4"
Filter bracket
Secure platform
to the floor
8"min.
for drain
access
Platform: 23-1/4"x 23-1/4"square Min.
load capacity:175 Ibs.
Outside wall
Plenum
cutout
32-1/4"H
x 20"W
Exterior/Outside
Bottom of case approx.2"
above bottom of plenum
Wall plenum
Bottom of case approx 2”
above bottom of plenum
Platform
Outside wall
Field supplied
outer flashing
•
4" min. from front of case - Unit
installed through FRONT of case.
•
5" min. from front of case - Unit
installed through SIDE of case.
•
3" min. from two sides of case.
(5"for side install).
31"
Side
View
2" min
10" max