Control Specifications: Intelligent Control (I Type)
I/O Port Definitions
I/O
Code
Description
Analogue
Input
Return air sensor
AI1
Return air temperature (Tr)
2-pipe coil circuit
sensor
AI2
Water inlet temperature sensor (Ti1)
Hot water Sensor
AI3
Water outlet temperature sensor (Ti2)
Input
LED display / IR
receiver
X-DIS 1
Digital communication port to LED display / IR receiver board.
Wired wall pad
TTL1
Digital communication port to wired wall-pad board.
Digital input
Occupancy contact
ON/OFF
NO/NC contact by setting
Float switch
Float
Voltage-free (NC).
The contact is connected with float switch (NC);
Electric Heater safety
switch
EH
Voltage-free (NC).
The contact is connected with E-heater safeties.
Power input
Phase
L1
Power supply to the PCB;
Neutral
N1
Power supply to the PCB;
Earth
PE1
Power supply to the PCB;
Voltage
output
Fan 1
CN4
Fan 1 driver
Fan2
CN5
Fan 2 driver
Valve1
MTV1
On/off valve
Valve2
MTV2
On/off valve
Water pump
WP
Voltage output (L), Power supply to condensate pump.
Voltage of Electric
Heater (Live)
L-EH
Voltage output (L), maximum 30A.
Stepping motor
CN1-2
Power supply to louver stepping motors.
output
Cooling signal contact.
AUX1
Voltage free contact. Maximum load 5A.
Heating signal contact.
AUX2
Voltage free contact. Maximum load 5A.
24VAC power input
DA1
24VAC external power supply (modulating valve applications only).
Modulating valve control
DA2
0~10Vdc
Modulating valve control
DA3
0~10Vdc
In Modbus signal
AB
Modbus port
Out Modbus signal
AB