Cardox Techical Manual
Page 18
Problem
Cause
Solution
Pump cycles without "deadhead-
ing."
CO2 bottle may not be connected.
Bottle may not have siphon tube.
Bottle is empty.
Check CO
2
supply to insure liquid
is
supplied to the pump.
Invert bottle for gravity feed of
liquid or replace with siphon tube
bottle.
Replace empty bottle.
Tubes do not reach minimum
weight.
Low air pressure to pump.
Adjust air pressure to 80–100
PSI. The higher the air pressure
the greater volume of CO
2
will be
conveyed to the tube. Adjust air
regulator at pump inlet to maximize
application of available plant air.
Pump will not operate.
Pump not primed.
Pump not funcitioning.
Follow procedure to prime
pump.
Pump will need to be repaired. Call
Pneumat and a loner pump will be
sent overnight to your facility.
If Cardox is required while the
pump is out of service, bypass the
pump with the bottle discharge
fill line. Connect the fill line direct
to the pump stand assembly inlet
nipple. Use the liquid CO
2
in the
bottle to chill the Cardox firing
tube,
bleed CO
2
into and out of the fir
-
ing tube until liquid CO
2
is readily
discharged from the tube (two to
four cycles). Then, weigh tube to
insure proper weight.
6. TROUBLESHOOTING
Содержание Cardox CO2
Страница 1: ...A B C D 8 7 6 TECHNICAL MANUAL 110 Mohr Drive Mankato MN 56001 1 800 458 9446 www pneumat com ...
Страница 22: ...Cardox Techical Manual Page 22 5780 0005 Cardox Fill Stand Assembly Parts List ...
Страница 25: ...Cardox Techical Manual Page 25 5730 0003 Auto Fill Activating Head w Eyebolt Parts List ...
Страница 27: ...Cardox Techical Manual Page 27 Series 3700 Firing Head Tube Body Discharge Head Parts List ...
Страница 28: ...Cardox Techical Manual Page 28 Series 5700 Firing Head Tube Body Discharge Head Parts List ...