– 13 –
Manual P5/EP5 23740/98.10
11.
I/P Unit, EP5
WARNING! Units installed in hazardous areas must have proper approvals.
The I/P unit is mounted directly on top of the positioner unit.
No external air supply is needed since the I/P unit is supplied with air from the
positioner unit.
Port I on the positioner unit will be plugged when the I/P unit and the
appropriate gauge block gasket installed.The I/P unit accepts a 4-20 mA input
signal.
The I/P unit is equipped with a built in 30 micron filter (Fig 4).
Caution: Do not operate the unit without filter and filterplug installed.
Do not unscrew filterplug when the positioner is pressurized.
Span and Zero for the I/P converter is factory set
and can not be adjusted
1
2