14. Feedback Unit
See feedback module instructions for connections and calibration.
The P5 or EP5, Valve Control System, can easily be equipped with a Feedback
unit, model F5. This unit will mount directly on top of the Pneumatic positio-
ner replacing the positioner front cover. The O-ring located on the bottom of
the Feedback unit, F5, will provide the same sealing or draining capabilities
as the front cover. The indicator and front cover from the positioner unit can
then be installed on to the Feedback unit.
WARNING! Units installed in hazardous locations must have proper
approvals.
Installing the feedback unit.
— Remove the front cover, indicator, and Allen head screw from
the top of the positioner spindle.
— Install the drive coupling 4 and adjust the O-ring seal on the bottom in
either sealed or draining position. (See section 6, page 10).
— Install the Feedback unit 9 on top of the Positioner unit, making
sure the coupling is properly engaged before tightening the four
screws 5.
— Make electrical connections and tighten cable glands.
(See F5 manual for details).
— Adjust cams and/or potentiometer to desired position.
— Install the indicator and front cover.
9
5
O-ring seal
4
3
2
Содержание EP5
Страница 1: ... 1 Manual P5 EP5 23740 98 10 Manual P5 EP5 PMV Valve Control System alve Control System ...
Страница 22: ... 22 Manual P5 EP5 23740 98 10 17 Exploded Drawing 98 9 84 ...
Страница 24: ... 24 Manual P5 EP5 23740 98 10 Approvals E5 IS EU ...
Страница 25: ... 25 Manual P5 EP5 23740 98 10 Approvals E5 EX EU ...
Страница 26: ... 26 Manual P5 EP5 23740 98 10 Approvals E5 IS US E5 EX US 1 ...
Страница 27: ... 27 Manual P5 EP5 23740 98 10 Approvals E5 IS US E5 EX US 2 ...
Страница 29: ... 29 Manual P5 EP5 23740 98 10 FM ...
Страница 30: ... 30 Manual P5 EP5 23740 98 10 CSA ...
Страница 31: ... 31 Manual P5 EP5 23740 98 10 CENELEC ...