31
7.
Set the specific trigger levels, then save settings by selecting
[Set Thresholds]
a.
The settings should match the Alerts set previously in the Notification List
b.
Averaging Window - Defines the number of seconds over which the input values will be
averaged before they are used to test against the threshold values.
[1(disabled) - 1800
seconds]
c.
Holdoff Time - Defines the number of seconds over which the input values will be averaged
before they are used to test against the threshold values.
[1(disabled) - 1800 seconds]
d.
Hysteresis - The hysteresis value does not have any units associated with it. It is a numeric value
ranging from
0-100
that will assume the units of each individual threshold. It is used as a pad
value that defines a narrow band above and below each threshold. A measurement must
exceed the programmed threshold plus (or minus) the hysteresis value in order for that
measurement to be used for alert triggering.