Wiring Precautions
w
w
w
w
w
w
w
w
w
w
Before wiring, verify the label for correct model number and options. Switch
off the power while checking.
Care must be taken to ensure that maximum voltage rating specified on the
label are not exceeded.
It is recommended that power of these units to be protected by fuses or circuit
breakers rated at the minimum value possible.
All units should be installed inside a suitably grounded metal enclosure to
prevent live parts being accessible from human hands and metal tools.
All wiring must conform to appropriate standards of good practice and local
codes and regulations. Wiring must be suitable for voltage, current, and
temperature rating of the system.
The " stripped " leads as specified in the Figure below are used for power and
sensor connections.
Beware not to over-tighten the terminal screws.
Unused control terminals should not be used as jumper points as they may
be internally connected, causing damage to the unit.
Verify that the ratings of the output devices and the inputs as specified in
Chapter 8 are not exceeded.
Electric power in industrial environments contains a certain amount of noise in
the form of transient voltage and spikes. This electrical noise can enter and
adversely affect the operation of microprocessor-based controls. For this
reason we strongly recommend the use of shielded thermocouple extension
wire which connects the sensor to the controller. This wire is a twisted-pair
construction with foil wrap and drain wire. The drain wire is to be attached to
ground at one end only.
4.5
7.0 mm
0.18"
0.27"
~
~
2.0mm
0.08" max.
Lead Termination
Connection Diagram
1
2
3
4
5
6
7
8
9
10 11
12 13 14
+
-
N
L
+
+
-
Measuring output
or
RS 485 Interface
Supply
volt
age
90-264
VAC
or 11
-28
VUC
2 A / 240 VAC Relay
or
5 V / 30 mA Logic
or
0(4)-20 mA Continuous
or
0-10 V Continuous
Control output OUT1
ALM2
(OUT2)
OUT1
ALM1
Logic
5V
/100
mA
+
-
-
Universal input
INP 1
INP 2
-
+
mA / V
TX1
TX2
-
+
W / W2
or
or
Wext (V)
Current transformer
2 A/240 VAC