9499 040 61241
2
Mini Jumper and DIP Switch
Front
Panel
Rear
Terminal
Access Hole
Controller chassis view below
1
ON
DIP
23
4
When the unit leaves the factory, the DIP switch is set so that TC & RTD are selected
for input 1 and all parameters are unlocked. Lockout function is used to disable the
adjustment of parameters as well as operation of calibration mode.
However the menu can still be viewed even if under lockout condition.
SEL1- SEL5 represent those parameters which are selected by using SEL1, SEL2,...
SEL5 parameters contained in Setup menu. The selected parameters are then
allocated at the beginning of the user menu.
*
TC, RTD, mV
0-1V, 0-5V, 1-5V, 0-10V
0-20 mA, 4-20 mA
Input 1
Select
All parameters are Unlocked
Only SP1, SEL1 SEL5 are unlocked
Only SP1 is unlocked
All Parameters are locked
Lockout
1
2
3
4
DIP Switch
:ON
:OFF
Factory Default Setting
*
Operating Instructions KS10-I