The same linearization table is used for input 1 and input 2.
6.2
Input scaling
Scaling of input values is possible. After any linearization, measurement value correction is according to the offset or
two-point method.
g
When using current or voltage signals as input variables for
InP
.x, the input and display values should
be scaled at the parameter level. Specification of the input value of the lower and upper scaling point is in
units of the relevant physical quantity.
g
Parameters
InL
,
OuL
,
InH
and
OuH
are visible only with
ConF
/
InP
/
Corr
=
3
selected.
Parameters
InL
and
InH
determine the input range.
Example with mA:
InL
= 4 and
InH
= 20 means that measuring from 4 to 20 mA is required (life zero setting).
Functions
20
Input scaling
UNIFLEX CI 45
mA/V
phys.
size
mA / V
phys. size
OuH
.x
OuL
.x
InH.
x
InL.
x
Example for mA/V
Ou.32
Ou.1
.
.
.
.
.
.
In.1
In.32