Latched alarms Lim1/2/3 (E element displayed) can be acknowledged, i.e. reset via digital alarm di1.
For Configuration, see page 46:
ConF
/
LOGI
/
Err.r
g
When an alarm is still pending, i.e. unless the error cause was removed ( E display blinks), latched alarms
cannot be acknowledged and reset.
g
If sensor errors should not be on the error list any more after error correction without manual reset in the
error list, suppression via BlueControl is possible by means of setting ILat.
CONF / othr / ILat
1
blocked
This setting is without effect on limit values Lim.1 … 3 configured for storage.
6.17
Reset to factory setting
In case of faulty configuration, UNIFLEX CI 45 can
be reset to its factory setting.
Ü
For this, the operator must keep the keys
increment and decrement pressed during
power-on.
*
For confirmation, press key increment to
select
YES
Ö
Confirm factory resetting with Enter and the
copy procedure isl started (display
COPY
).
ä
Afterwards the device restarts.
In all other cases, no reset will occur(timeout
abortion).
g
If one of the operating levels was blocked,
reset to factory setting is not possible.
g
If a pass number was defined (via
BlueControl
®
) but no operating level was
blocked, enter the correct pass number
when prompted in
3
. A wrong pass numbers
aborts the reset action.
g
The copy procedure (
COPY
) can take some
seconds.
Now, the transmitter is in normal operation.
Functions
UNIFLEX CI 45
Reset to factory setting
37
Error-state
Signification
2
Pending error
Change to error status
1
after error removal
1
Stored error
Change to error status 0 after acknowledgement in error list
0
0
no error/message
Not visible, except during acknowledgement
FAC
torY
FAC
no