S MA RT SC AN
®
•
In such a position that it is difficult or dangerous to reach for testing or maintenance or where
children can easily tamper with the alarm
•
In an area where water or other liquids may enter the alarm, except in the extremely unlikely case
that the alarm and its connections are waterproof.
•
On surfaces subject to significant vibration.
IMPORTANT:
This version of Automist Smartscan will not function correctly if activated by smoke detection
or a manual call point. Use only fixed temperature heat detection. Use with other types of detection could
lead to death or injury.
Ensure Automist Smartscan is only connected to the main heat alarm(s) in the volume it protects. You can
check these interconnections using the product’s ALARM TEST MODE (see page
44). In this mode, the alarm
lamp will light to indicate a functioning alarm input. Ensure that Automist Smartscan has been successfully
returned to the System OK state following this test, and that the water supply remains open, and that
nozzles are unobstructed.