39
This is the mixer step value. Increasing its
value will speed up reaching of the preset
mixer temperature, yet too high a value of
this parameter will cause over-regulation of
temperature and unnecessary movement of
the servo, thus shortening its life-span.
It is recommended to set this parameter
within the range of 2
–
6 [by default: 3].
16.5
Integration time constant
Caution:
it is recommended not to
modify this parameter.
This
parameter
influences
the
mixer
standstill time if the temperature measured
by the mixer sensor is close to the preset
mixer temperature. Greater value will cause
longer standstills of the servo. Too high a
value extends the time by which the servo
can find the preset temperature. Setting too
low values can cause over-regulation of
temperature and faster wear of the servo.
It is recommended to set this parameter
within the range of 80
–
140 [by default:
110].
16.6
Valve opening time
Enter the time of full valve opening, which
can
be
found
in
the
valve
servo
documentation.
16.7
Increase in boiler temperature on
account of MIXER
If the preset boiler temperature is lower than
the preset mixer temperature, the regulator
shall automatically assume the preset boiler
temperature equal to the preset mixer
temperature plus value of the parameter
increase preset CH temp. to DHW.
This parameter can be found in MENU ->
SERVICE SETTINGS -> CH/DHW SETTINGS
17
RESTORING SERVICE SETTINGS
In order to restore default service settings,
place the cursor on the „YES” option and
press the “TOUCH and PLAY” knob.
Drawing 45 Default service settings
Restoration of the factory settings
will also restore user settings.