background image

37 

 

off.  Detailed  information  can  be  found  in 
point 13.12. 

14.17

 

Alarms 

 signalling setup 

Detailed information can be found in point 
13.13 

14.18

 

Boiler cooling temperature 

The  temperature  at  which  the  boiler  is 
preventatively 

cooled 

down. 

Detailed 

description can be found in point 19.3. 

 

It  is  suggested  to  set  the 

boiler 

cooling  temp. 

below  the  value  of 

activating  the  safety  temperature 
limiter, 

which 

will 

prevent 

interruptions  in  the  boiler  work  due 
to overheating. 

15

 

CH and DHW SERVICE SETTINGS 

15.1

 

CH start temperature 

This  parameter  specifies  the  temperature  at 
which  the central  heating  pump  is  activated. 
After  reaching  the  temperature  equal  to  the 

CH  start  temp.

  parameter,  the  central 

heating  pump  is  activated.  This  protects  the 
boiler  against  retting  caused  by  its  being 
cooled down by hot water returning from the 
system. 

 

Disabling  the  CH  pump  on  its  own 
does  not  guarantee  protecting  the 
boiler  against  retting,  and  the 
resulting corrosion of the boiler. Use 
additional  automatics,  e.g.  a  four-
way valve. 

15.2

 

CH pump standstill time 

This  parameter  determines  the  central 
heating  pump  down-time  after  it  is  blocked 
by  disconnected  room  thermostat,  at  the 
moment 

of 

reaching 

preset 

room 

temperature  (point  13.11).  As  a  result  of 
blocking  the  central  heating  pump,  the 
temperature  in  the  heated  rooms  will  drop, 
and  the  boiler  will  reach  the  preset 
temperature  faster,  and  then  switch  to  the 
CONTROL  mode.  Yet,  too  long  a  blockade  of 
the  central  heating  pump  will  cause  the 
system 

to 

cool 

down, 

which 

is 

disadvantageous  for  maintaining  the  room 
temperature  at  constant  level.  The  heating 
medium accumulated in the system has high 

thermal  inertia,  and  heating  it  after  the 
thermostat contacts are shorted can take too 
long.  Thus,  it  is  not  recommended  to  set 
excessively long central heating pump down-
times.  After  the 

CH  standstill  time

,  the 

regulator  will  enable  it  for  a  constant,  pre-
programmed  time of 30 s.  Caution: Blocking 
the CH pump can make the boiler overheat. 

15.3

 

CH pump standstill with DHW priority 

Prolonged filling of the DHW tank when DHW 
priority  is  enabled  can  cause  extensive 
cooldown  of  the  CH  system,  as,  with  these 
settings, the CH pump is disabled. 
The parameter 

CH stand. load DHW 

prevents 

this  by  enabling  periodical  activation  of  the 
CH pump while the DHW tank is being filled. 
After  this  time,  the  CH  pump  will  be 
activated for a constant, programmed time of 
30s. 

15.4

 

Maximum DHW temperature 

This  parameter  specifies  to  what  maximum 
temperature  will  the  DHW  tank  be  heated  in 
the case of dropping excessive heat from the 
boiler  during  an  emergency.  This  parameter 
is  very  important,  as  setting  it  at  too  high  a 
value can scald the users. Too low a value of 
this  parameter  will  make  it  impossible  to 
channel  excessive  heat  to  the  DHW  tank  if 
the boiler overheats. 

 

When  designing  the  domestic  hot 
water  system,  the  possibility  of 
regulator  malfunction  should  be 
taken into consideration. As a result 
of  malfunction  of  the  regulator,  the 
water in the DHW tank can become 
dangerously  hot,  threatening  the 
users with scalding. 

THEREFORE, ADDITIONAL SAFEGUARDS - 

THERMOSTATIC VALVES - SHOULD BE 

USED. 

15.5

 

DHW tank hysteresis 

Below  the 

preset  DHW  temp. 

  DHW  cont. 

hysteresis 

the  DHW  pump  is  activated  in 

order to fill the DHW tank. 
 

Содержание ecoMAX 80 R1

Страница 1: ...EL FIRED BOILERS WITH FEEDING SCREW SERVICE AND ASSEMBLY MANUAL ISSUE 1 2 APPLICABLE TO SOFTWARE MODULE PANEL v06 11 030 v06 10 014 v06 11 031 v06 10 015 v06 11 035 v06 10 016 v06 11 036 v06 10 017 v0...

Страница 2: ......

Страница 3: ...ION RATE 27 13 6 CONNECTING ELECTRICAL SYSTEM 27 13 7 PROTECTIVE CONNECTIONS 28 13 8 CONNECTING TEMPERATURE SENSORS 29 13 9 CONNECTING WEATHER SENSOR 29 13 10 CHECKING TEMPERATURE SENSORS 29 13 11 CON...

Страница 4: ...AGE TO BOILER TEMP SENSOR 41 18 5 FEEDER TEMPERATURE SENSOR DAMAGE 41 18 6 NO COMMUNICATION 41 19 EXTRA FUNCTIONS 43 19 1 POWER SUPPLY DECAY 43 19 2 PROTECTION AGAINST FREEZING 43 19 3 PREVENTIVE COOL...

Страница 5: ...facturer should check if the regulator s mating with the given boiler type is proper and whether it can cause danger The regulator is not an intrinsically safe device which means that in the case of m...

Страница 6: ...ve way Regulator can cooperate with an additional control panel situated in living quarters It can be used in a household and similar facilities as well as in light industrialized facilities 3 Informa...

Страница 7: ...REGULATOR INSTRUCTION MANUAL ecoMAX 800 model R1...

Страница 8: ...mp mode DHW cont hysteresis DHW disinfection Mixer 1 settings Mixer 2 settings Mixer 3 settings Clock Screen brightness Language Feeder Manual Restore default val Service settings Feeder Fan CH pump D...

Страница 9: ...to active intervals W symbol of increase in the preset boiler temperature for the time of filling the domestic hot water DHW tank M symbol of increasing the preset boiler temperature due to mixer cycl...

Страница 10: ...mode the CH pump is turned off which can increase the boiler temperature 8 6 FIRING UP Enter the LIGHT mode by selecting the LIGHT operation mode and pressing the TOUCH and PLAY button The LIGHT mode...

Страница 11: ...tandard mode described in this section of the manual and automatic setting Fuzzy Logic1 1 Fuzzy Logic available only in special versions of the regulator In order to enable the Standard regulation mod...

Страница 12: ...gulator automatically switches into the CONTROL mode 8 8 OPERATION Fuzzy logic settings After switching the boiler adjustment mode from Standard to Fuzzy Logic the regulator works in the OPERATION mod...

Страница 13: ...earing in mind that too long an interval can make the furnace fall in during the boiler standstills yet setting an insufficient time will lead to an increase in the boiler temperature The feeder and a...

Страница 14: ...ic hot water temperature can be also set at the main window Press the TOUCH and PLAY knob in the main window The preset boiler temperature flashes press the knob again to make the DHW temperature flas...

Страница 15: ...select a proper heating curve Guidelines for setting proper heating curve floor heating 0 2 0 6 radiator heating 1 0 1 6 boiler 1 8 4 Drawing 15 heating curves Tips for selecting appropriate heating...

Страница 16: ...ture unchanged Between 22 00 and 23 59 the regulator will lower the preset boiler temperature by 3 C The time period is skipped if its decrease value is 0 even if hours are specified Decrease in the p...

Страница 17: ...verheat 8 20 Manual control The regulator provides a possibility of manual activation of an executive device e g a pump feeder motor or blower Thanks to this functionality you can check whether the gi...

Страница 18: ......

Страница 19: ...REGULATOR INSTALLATION AND SERVICE SETTINGS MANUAL ecoMAX 800 model R1...

Страница 20: ...Max boiler temp Min fan power CH system type Room thermostat Out temp control Heating curve Fuel detect time Feed time CONTR Extend fan time Max feeder temp Min return temp Return temp hysteresis Ret...

Страница 21: ...ngs 2 Integr time const Valve opening time Mixer operat Min mixer temp Max mixer temp Proportional band OFF CH ON Floor h ON Pump only Mixer settings 3 Integr time const Valve opening time Mixer opera...

Страница 22: ...its operation only after the boiler exceeds the CH pump start temp by default 40 O C Mixer pump and servo start operation regardless of the value of the parameter CH pump start temp The mixer servo 1...

Страница 23: ...on service settings boiler settings Heating curve 1 8 4 service settings boiler settings Brief description The CH pump 11 and the DHW pump 12 can start their operation only after the boiler exceeds t...

Страница 24: ...o C cuts off power supply of mixer pump when the maximum temperature is exceeded the thermostat is not part of the ecoMAX 800 regulator set 27 return temperature sensor 28 thermostatic three way valve...

Страница 25: ...direct effects of weather i e rain and sunlight Storage and transport temperature cannot exceed the range of 15 65 C During transport the device cannot be exposed to vibrations greater than those typi...

Страница 26: ...re of the panel surroundings will be lowered in such case use other methods 13 4 Executive module installation The enclosure must provide protection rate appropriate for the environmental conditions i...

Страница 27: ...tallation Drawing 29a provides and explanation After enclosing in accordance with this drawing the device has protection rate IP 20 from the front side of the executive module enclosure specified on t...

Страница 28: ...al strip contacted with the metal casing of the regulator The fitting should be connected to the regulator terminal marked with symbol and with grounding terminals of the devices connected to the regu...

Страница 29: ...to temperature up to 100 C 13 9 Connecting weather sensor The regulator cooperates only with a weather sensor of the CT4 P type The sensor should be installed on the coldest wall of the building usua...

Страница 30: ...the purposes of precise adjustment of temperature in the heated rooms it is possible to enable blockade of the CH pump by disconnection of contactors of the room thermostat In order to enable the CH...

Страница 31: ...sabled Drawing 36 Enabling control of a reserve boiler MENU SERVICE SETTINGS BOILER SETTINGS AUXILIARY BOILER Auxiliary boiler off temperature Control over a reserve boiler is disabled if the aforemen...

Страница 32: ...de free gravitational flow of water in the boiler cycle the effective diameter of the switching valve 4 must be greater or equal to the diameter of the boiler cycle pipe 7 The presented hydraulic diag...

Страница 33: ...2 and AL4 sum up the values corresponding to individual alarms i e you should set 2 8 10 If alarms AL1 AL2 and AL3 are to be signalled set the parameter to 7 as 1 2 4 7 13 14 Connecting mixer The regu...

Страница 34: ...that a safety temperature limiter is used 13 16 Connecting additional panel It is possible to connect an additional control panel situated in the living quarters e g in a kitchen The additional panel...

Страница 35: ...ons Detailed information can be found in point 8 16 and 13 9 14 4 Heating curve This parameters allows selection of appropriate heating curve Detailed information can be found in point 8 16 Drawing 44...

Страница 36: ...ow operation In the CONTROL mode after feeding a dose of fuel and disabling the feeder the fan continues to work for the time of extend fan time in order to light up the supplied fuel in accordance wi...

Страница 37: ...ous for maintaining the room temperature at constant level The heating medium accumulated in the system has high thermal inertia and heating it after the thermostat contacts are shorted can take too l...

Страница 38: ...n Do not enable this option if the system is made of pipes vulnerable to high temperature in such case we recommend setting the mixer to FLOOR h ON FLOOR h ON choose this option if the mixer cycle fee...

Страница 39: ...etting too low values can cause over regulation of temperature and faster wear of the servo It is recommended to set this parameter within the range of 80 140 by default 110 16 6 Valve opening time En...

Страница 40: ...tion against boiler overheating is twofold First after exceeding the boiler cooling preventive temp by default 90 C the regulator tries to decrease the boiler temperature by dropping the excessive hea...

Страница 41: ...ting the regulator Check the sensor and possibly replace it The method of checking the temperature sensor is described in point 13 10 Drawing 48 View of alarm boiler temperature sensor failure 18 5 Fe...

Страница 42: ...42 parameters If an alarm occur it will take action in accordance with the given alarm Check the lead connecting the control panel with the executive module and replace or repair it...

Страница 43: ...the boiler is not in use This function can be enabled also when the regulator is turned off via keyboard regulator in STAND BY and in the STOP mode 20 REPLACEMENT OF PARTS AND SUBASSEMBLIES When orde...

Страница 44: ...ht after turning the regulator on Drawing 52 View of display after turning the regulator on where 1 control panel software number 2 executive module software number The regulator can operate improperl...

Страница 45: ...e fan power parameter fan power check if the safety temperature limiter STB jumper is on terminals 1 2 the jumper should be placed only if no temperature limiter is connected if the boiler manufacture...

Страница 46: ...in the DHW SUMMER mode the heaters are hot and the boiler overheats Increase the parameter Extend DHW pump time in order to cool down the boiler 10 the DHW pump is active even if the DHW tank has been...

Страница 47: ...eed to be arranged between the boiler manufacturer and the PLUM sp z o o company After fitting the regulator the boiler manufacturer selects the boiler type which causes loading of default values This...

Страница 48: ...rature It is possible to record data from 1024 days back that is from about 3 years You can clear the data from the regulator memory only after connecting the regulator to a computer In order to enter...

Страница 49: ...name 1 No fuel 2 Boiler overheated 3 Flame recessed to retort 4 Boiler temperature sensor damage 5 Feeder temperature sensor damage Caution A temperature record of about 108 C is an evidence that the...

Страница 50: ......

Страница 51: ......

Отзывы: