Operating Principle:
Magnetic-inductive flow measurement is based on Faraday´s
law of induction. The liquid to be measured (electrically
conductive) flows perpendicular to a magnetic field. This induces
an electrical voltage in the liquid.
This is picked up by two electrodes inserted in the measuring
tube and further processed by the downstream electronics. The
voltage level is proportional to the flow velocity.
Materials:
Measuring tube:
PEEK-GF30
Process connections:
stainless steel 1.4571
Electrodes:
stainless steel 1.4571
O-rings
EPDM / FKM (optional)
Housing:
Aluminum die casting
Technical Data:
Characteristics D = Ø 7 mm
D = Ø 10 mm
D = Ø 20 mm
Nominal sizes
DN 7
DN 10
DN 20
Process-
connection
G ½ male
G ½ male or
G ¾ male
G 1 male
Measuring
range
0,5...30 l/min
1...60 l/min
5...250 l/min
Signal output
from approx.
0,4 l/min
from approx.
0,9 l/min
from approx.
4 l/min
Accuracy
+/- 1,5 % of measured value +/- 0,3 % of final value
Repeatability
1 %
Response time
<500 ms
Conductivity of
the medium
Min. 50 µS/cm
T
medium
5...90 °C
T
environment
5...70 °C
Nominal
pressure
PN 16
Flow display
LED green, flashes proportional to flow rate
Protection
class
IP65
Electrical Data
El. connection
round plug M12x1
Supply voltage
24 VDC (+/-10 %)
Power input
< 150 mA
Frequency output
Pulse rate:
1000 pulses/l
(standard)
factory
configurable:
1...2000
pulses/l
500 pulses/l
(standard)
factory
configurable:
1...1000 pulses/l
100 pulses/l
(standard)
factory
configurable:
1...200 pulses/l
Disbanding:
1,0 ml/pulse
(standard)
factory
configurable:
1000...0,5
ml/pulse
2,0 ml/pulse
(standard)
factory
configurable:
1000...1
ml/pulse
10 ml/pulse
(standard)
factory
configurable:
1000...5
ml/pulse
Signal form:
square-wave signal, duty cycle 50:50, Push-Pull
scanning
Signal current:
Max. 100 mA, current-limited
Analogue output 4...20 mA:
Corresponds to
flow rate *
0...20 l/min
or
0...30 l/min
0...40 l/min
or
0...60 l/min
0...200 l/min
or
0...250 l/min
Max. load:
250 Ω against GND
Analogue output 0...10 V
Corresponds to
flow rate *
0...20 l/min
or
0...30 l/min
0...40 l/min
or
0...60 l/min
0...200 l/min
or
0...250 l/min
* other ranges available on request