20
Type of input
Dip-switch Notes
0..1V
0..20 mV
Connect positive signal to analog
input and reference signal to pin
AI-COM.
0..20 mA
Connect positive signal to analog
input and any reference pin to the
ground of power supply for digital
outputs
4..20 mA
TC
K, S, T,
R, J, E
Connect positive signal of
thermocouple to the analog input
and the negative signal of
thermocouple to pin AI-COM.
PT100
NI100
For two-wires PT100/NI100 this
setting can be selected for all
inputs. Connect one wire to
analog input and the one to
reference pin of AI-COM inputs
For 3-wires PT100/NI100 this
setting is selectable only for
AI1 and AI4. Connect white wire
to analog input AI1 or AI4 and the
two red wires to the reference pin
of AI-COM e to the compensation
input of AI2 or AI3.
Compensa-
zione per
PT100/NI100
a 3 fili
For 3-wires PT100/NI100 this
setting is selectable only for AI2
and AI3, respectively as
compensation for inputs AI1 and
AI4.