50
If the corresponding port is set to a Master
protocol, this indicates the number of non-
received packets of information during the
communication.
At startup, all counts are initialized to 0.
R
SM108 1108
EXP1 number of errors
SM110 1110
COM2 number of errors
If the corresponding port is set to a Master
protocol, this indicates the number of packets
of information with errors during the
communication.
At startup, all counts are initialized to 0.
R
SM112 1112
EXP1 minimum delay for new transmission
SM113 1113
COM2 minimum delay for new transmission
If the corresponding port is set to a Master
protocol, this sets the minimum delay for a
new transmission after the reply of a slave
device.
Possible values 0…100
0…100ms,
default 5
5ms
R/W
SM120 1120
State of digital inputs I1÷I16 during test stage
This word sets the state of digital inputs
during test stage (SM0.5=1). Each bit of this
word corresponds to the state of one digital
input, starting with less significant bit
(SM120.0
I1, SM120.15
I16). This word is
automatically set to zero at the starting of
TD240.
R/W
SM121 1121
Filter on analog inputs I1÷I16
(default 10 means)
It is possible to filter digital inputs signals by
setting a delay time. If the state of input
changes, the new state will be accepted only
if the input will maintain it for the
programmed time. Data will be accepted
after that the filter will have eliminated noises
and fixed input lines on stable values.
TD240 supports filters with delay times
between 0 and 50 ms.
R/W
Содержание TD240 series
Страница 1: ...Manuale operatore...
Страница 2: ...2...
Страница 6: ...6 3 Mechanical dimensions and installation...
Страница 24: ...24 7 1 Starter Kit Connection of the terminal to the PC...
Страница 27: ...27 7 2 1 Creation of a new project...
Страница 89: ...89 11 Notes Updates...
Страница 90: ...90...
Страница 91: ...91...