Bit 11
This bit, if set ON, enables the serial
port COM2 in "modem" mode. That
means that the timeout between one
character and another in reception is
automatically fixed to 40 mS.
R/W
Bit 15
Bit ON to indicate a TD240-11AD;
bit set to zero to indicate a TD240-
AD
R
SM1
1001
Diagnostic bit anomaly / malfunction
Bit 0
Bit ON in case of loss of data kept in
the area “special marker” SM.
R/W
Bit 1
Bit ON in case of loss of data kept in
the area “variable V”.
R/W
Bit 2
Bit ON in case of loss of data kept in
the area “EEProm”.
R/W
Bit 3
Bit ON in case of program load from
flash memory.
R/W
Bit 4
Bit ON in case of reset of the CPU or
intervention of the watch-dog.
R/W
Bit 5
Bit ON in case of stack overflow in
the area reserved for RAM.
R/W
Bit 6
Bit ON in case of missing calibration
of analog inputs/ outputs
R/W
Bit 7
Bit ON in case of anomaly /
malfunction in the EEProm.
R/W
Bit 8
Bit ON in case of anomaly /
malfunction in the clock.
R/W
Bit 9
Bit
ON
in
case
of
anomaly/
malfunction in t
he analog digital
converter 16 bits
R/W
Bit 10
Bit ON in case of stack overflow of
the timer interrupt
R/W
Bit 11
Bit ON in case of lost calibration data
for analog input/ output.
R/W
Bit 12
Bit ON if analog input AI1 out of
range.
R
Bit 13
Bit ON if analog input AI2 out of
R
Содержание TD240 series
Страница 1: ...Manuale operatore...
Страница 2: ...2...
Страница 6: ...6 3 Mechanical dimensions and installation...
Страница 24: ...24 7 1 Starter Kit Connection of the terminal to the PC...
Страница 27: ...27 7 2 1 Creation of a new project...
Страница 89: ...89 11 Notes Updates...
Страница 90: ...90...
Страница 91: ...91...