40
SM103
1103 Delay answer/wait incoming data COM1 (def.20ms)
SM113
1113 Delay answer/wait incoming data
EXP1
(def. 20ms)
SM123
1123 Delay answer/wait incoming data
COM2
(def. 0ms)
With slave protocol this word defines min. delay
between end of data receiving from master device and
the start of answer transmission form PL260 (max.
100ms).
With master protocol this word define max. waiting
between start of query transmission from PL260 and
full receiving of answer from slave device.
Value is expressed in ms.
R/W
SM104
1104 Delay new master transmission COM1 (default 5 ms)
SM114
1114 Delay new master transmission
EXP1
(default 5 ms)
SM124
1124 Delay new master transmission
COM2
(default 5 ms)
With master protocol this word defines min. waiting
between end of data receiving (from slave to master),
and start of transmission for a new query from master
to slave.
With slave protocol this value is not used.
Value is expressed in ms, range 0-100 ms.
R/W
SM105
1105 Number of errors for signal on status
COM1
(def. 10)
SM115
1115 Number of errors for signal on status
EXP1
(def. 10)
SM125
1125 Number of errors for signal on status
COM2
(def. 10)
Value entered for this word defines:
If master protocol - the number of consecutive
communication errors after which the anomaly is
notified in the relevant bit of “serial status”.
If slave protocol - the time in seconds after that the
anomaly is notified keeping to "1" all bit of the word
"serial status".
R/W
Содержание PL260
Страница 1: ...User manual...
Страница 2: ...2...
Страница 8: ...8 1 4 Size and installation 90 160 mm 43 53 5 45...