30
- DRR460 -
User manual
114
se.de.
Serial Delay
(Word modbus 2114)
Selects the serial delay.
0...100 ms.
Default
: 0 ms.
115
off.L.
Off Line
(Word modbus 2115)
Selects the off-line time. If no communication is available within the selected time, the controller
will switch-off the command output.
0
Offline disabled (
Default
)
1...6000 tenths of seconds (Es. 100 = 10.0 s)
116÷120
Reserved Parameters - Group I
Reserved parameters - Group I
GROUP J - EXPANSION
121
E.Mod.
Expansion Module
(Word modbus 2121)
Enables
“Expansion module”
mode
0
Disabled (
Default
)
1 Enabled
122
i.vA.o.
Initial Value Output
(Word modbus 2122)
Selects output state at starting
Bit 0
Q1 (0 = off; 1 = on)
Default
: 0
Bit 1
Q2 (0 = off; 1 = on)
Default
: 0
123
E.Mo.o.
Error Mode Output
(Word modbus 2123)
Defines if the output has to commute into a default state in case of error or off-line. If the error is
eliminated, the output keeps the default state.
Bit 0
Q1 (0 = unvaried; 1 = commute)
Default
: 0
Bit 1
Q2 (0 = unvaried; 1 = commute)
Default
: 0
124
E.vA.o.
Error Value Output
(Word modbus 2124)
Defines values to be assumed by the outputs in case of error or off-line.
Bit 0
Q1 (0 = off; 1 = on)
Default
: 0
Bit 1
Q2 (0 = off; 1 = on)
Default
: 0
125
A.o.ty.
Analogue Output Type
(Word modbus 2125)
Select the type of Analogue Output
0
0...20 mA
1
4...20 mA (
Default
)
126
L.L.A.o.
Lower Limit Analogue Output
(Word modbus 2126)
Analogue output lower limit range (value related to 0/4 mA)
-32767..+32767 [digit]
Default
: 0.
127
u.L.A.o.
Upper Limit Analogue Output
(Word modbus 2127)
Analogue output upper limit range (value related to 20 mA)
-32767..+32767 [digit]
Default
: 10000.
128
i.v.A.o.
Initial Value Analogue Output
(Word modbus 2128)
Selects analogue output value at starting
-32767..+32767 [digit]
Default
: 0.