User manual - DRR460 -
29
101
re.ty.
Retransmission Type
(Word modbus 2101)
Select the type of Retransmission
0
0...20 mA
1
4...20 mA (
Default
)
102
Lo.L.r.
Lower Limit Retransmission
(Word modbus 2102)
Linear output lower limit range (value related to 0/4 mA)
-32767..+32767 [digit] (degrees for temperature sensors),
Default
: 0.
103
up.L.r.
Upper Limit Retransmission
(Word modbus 2103)
Linear output upper limit range (value related to 20 mA)
-32767..+32767 [digit] (degrees for temperature sensors),
Default
: 10000.
104
re.s.e.
Retransmission State Error
(Word modbus 2104)
Selects the value of the analogue output in Volt in case of error
0
0 mA (
Default
)
1
4 mA
2
20 mA
3
21.5 mA
105
re.s.S.
Retransmission State Stop
(Word modbus 2105)
Defines the analogue output value with controller in STOP
0
0 mA (
Default
)
1
4 mA
2
20 mA
3
21.5 mA
4
Retransmission active in STOP
106÷110
Reserved Parameters - Group H
Reserved parameters - Group H
GROUP I - SERIALS
111
sL.ad.
Slave Address
(Word modbus 2111)
Selects slave address for serial communication when all DIP 1 contacts are set on OFF
1...254.
Default
: 247.
112
bd.rt.
Baud Rate
(Word modbus 2112)
Selects slave address for serial communication when all DIP 2 contacts are set on OFF
0
4800 bit/s
1
9600 bit/s
2
19200 bit/s (
Default
)
3
28800 bit/s
4
38400 bit/s
5
57600 bit/s
6
115200 bit/s
113
s.p.p.
Serial Port Parameters
(Word modbus 2113)
Selects the type of format for the modbus RTU communication
0
8-N-1
8 bit, no parity, 1 stop bit (
Default
)
1
8-E-1
8 bit, even parity, 1 stop bit
2
8-O-1
8 bit, odd parity, 1 stop bit
3
8-N-2
8 bit, no parity, 2 stop bit
4
8-E-2
8 bit, even parity, 2 stop bit
5
8-O-2
8 bit, odd parity, 2 stop bit