26
- DRR460 -
User manual
57
A.I.5.o
Alarm 1 State Output
(Word modbus 2057)
Alarm 1 output contact and intervention type.
0
(N.O. Start) Normally open, active at start (
Default
)
1
(N.C. Start) Normally closed, active at start
2
(N.O. Threshold) Normally open, active on reaching alarm
3
(N.C. Threshold) Normally closed, active on reaching alarm
58
a.1.Hy.
Alarm 1 Hysteresis
(Word modbus 2058)
-10000..+10000 [digit] (degrees.tenths for temperature sensors).
Default
0.5.
59
a.1.s.e.
Alarm 1 State Error
(Word modbus 2059)
State of contact for alarm 1 output in case of error.
0
0 mA if alarm 1 on AO. Open contact if alarm 1 on Q1 or Q2.
Default
1
4 mA if alarm 1 on AO. Closed contact if alarm 1 on Q1 or Q2.
2
20 mA if alarm 1 on AO. Open contact if alarm 1 on Q1 or Q2
3
21.5 mA if alarm 1 on AO. Closed contact if alarm 1 on Q1 or Q2.
60
a.1.s.S.
Alarm 1 State Stop
(Word modbus 2060)
Alarm 1 output contact state with controller in STOP
0
0 mA if alarm 1 on AO. Open contact if alarm 1 on Q1 or Q2.
Default
1
4 mA if alarm 1 on AO. Closed contact if alarm 1 on Q1 or Q2.
2
20 mA if alarm 1 on AO. Open contact if alarm 1 on Q1 or Q2
3
21.5 mA if alarm 1 on AO. Closed contact if alarm 1 on Q1 or Q2.
4
Active alarm in Stop
61
a1.re.
Alarm 1 Reset
(Word modbus 2061)
Alarm 1 contact reset type.
0
Automatic reset (
Default
)
1
Manual reset (by word 1210)
2
Manual reset stored. (keeps relay status also after an eventual power failure)
62
a.1.de.
Alarm 1 Delay
(Word modbus 2062)
Alarm 1 Delay. -3600..+3600 seconds.
Default
: 0.
Negative: delay in alarm output phase.
Positive: delay in alarm entry phase.
63÷67
Reserved Parameters - Group D
Reserved parameters - Group D
GROUP E - ALARM 2
68
AL.2
Alarm 2
(Word modbus 2068)
The alarm intervention is related to Alarm 2.
0
Disabled (
Default
)
1
Absolute alarm (threshold) referred to process active above
2
Absolute alarm (threshold) referred to process active below
3
Band alarm
4
Upper deviation alarm
5
Lower deviation alarm
6
Absolute alarm referred to active setpoint above
7
Absolute alarm referred to active setpoint below
8
Status alarm (active in RUN / START)
9
Cold actuator auxiliary (Cold action in double loop)
10
Heater Break Alarm and Overcurrent Alarm
11
Sensor error. Active alarm in case of broken sensor
12
Remote. Alarm enabled by word 1212