User manual

 - DRR244 - 11

5.1.c 

CT input

CT

18

19

To enable CT input, modify parameter 287 

ct F

.

•  Input for 50 mA amperometric transformer.

•  Sampling time 100 ms.

•  Configurable by parameters.

5.1.d 

Digital inputs

0V

DI2

(PNP)

18

DI1

(PNP)

17

+V

16

9

Digital inputs can be enabled by parameters.

Close pin 

“DIx”

 on pin 

“+V”

 to enable digital input.

It is possible to put in parallel the digital inputs of different devices joining 

togheter the 0V pins (9).

5.1.e 

Serial input

RS485

Shield/Schermo

(B)

(A)

21

20

Modbus RS485 communication.

RTU Slave with galvanic insulation.

It is recommended to use the twisted and shielded cable for communica-

tions.

5.1.f 

Digital output

0V

DO1

(PNP)

DO2

(PNP)

9

10

19

Digital output PNP (including SSR) for command or alarm.

Range 12 VDC/25 mA or 24 VDC/15mA selectable by parameter 282 

v.out

5.1.g 

Analogue output AO1

AO1

V/mA

12

11

Linear output in 

mA 

or 

V

 (galvanically isolated) configurable as command, 

alarm or retransmission of process-setpoint.

The selection mA or Volt for the linear output depends on the parameters 

configuration.

5.1.h 

Relays output Q1 - Q2

3

2

1

Q1

5A

230V

6

5

4

Q2

5A

230V

Capacity 5 A / 250 VAC for resistive loads.

See chart below.

50

20

10

5

0

1

2

3

4

Contact load current (A)

5

Service life (x10

4

operations)

100

AC125 V

AC125V COS ø=0.4

DC30 V t=7ms

Life Curve

AC250V COS ø=0.4

DC30 V t=15ms

200

AC250V

DC30 V

Electrical endurance Q1, Q2:

•  5A, 250 VAC, resistive loads, 10

5

 operations.

•  20/2A, 250 VAC, cosφ = 0.3, 10

5

 operations.

Содержание DRR244

Страница 1: ...DRR244 Controller Regolatore r gulateur User manual Manuale d uso Manuel utilisateur...

Страница 2: ...conceived for applications related to nuclear power plants weapon systems flight control mass transportation systems Only qualified personnel should be allowed to use device and or service it and only...

Страница 3: ...shielded cables and using separate conduits or ducts is recommended Attach a surge suppressor or noise filter to peripheral devices that generate noise in particular motors transformers solenoids mag...

Страница 4: ...0 60 mV Pot Input 1 150 K CT 50 mA Tolerance 25 C 0 2 1 digit on F s for thermocou ple thermoresistance and V mA Cold junction accuracy 0 1 C C Impedence 0 10 V Ri 110 K 0 20 mA Ri 5 0 40 mV Ri 1 M R...

Страница 5: ...3 DRR244 FNC SET C1 C2 A1 A2 A3 TUN MAN REM 5 Electrical wirings This controller has been designed and manufactured in conformity to Low Voltage Directive 2006 95 EC 2014 35 EU LVD and EMC Directive 2...

Страница 6: ...at one side only AI1 PT NI100 Shield Schermo Rosso Red Bianco White Rosso Red 13 14 15 For thermoresistances PT100 Ni100 For the three wire connection use wires with the same section For the two wire...

Страница 7: ...ons 5 1 f Digital output 0V DO1 PNP DO2 PNP 9 10 19 Digital output PNP including SSR for command or alarm Range 12 VDC 25 mA or 24 VDC 15mA selectable by parameter 282 v out 5 1 g Analogue output AO1...

Страница 8: ...ameter value being inserted 6 1 Meaning of Status Lights Led 3 C1 ON when the command output 1 is active In versions with single analog input it is ON when the valve is opening In the versions with tw...

Отзывы: