background image

User manual

 - DRR244 - 9

3.4 

Programming mode

by keyboard

..see paragraph 

9

software LabSoftview

..on 

“Download section”

 of official pixsys site: www.pixsys.net

App MyPixsys

..through download the App on Google Play Store®, see paragraph 

8

When activated by a reader/interrogator supporting NFC-V protocol, 

controller DRR244 is to be considered a VICC (Vicinity Inductively 

Coupled Card) according to ISO/IEC 15693 and it operates at a frequency 

of 13.56 MHz. 

The device does not intentionally emit radio waves

.

Dimensions and Installation

Extractable terminal blocks

Morsettiere Estraibili

72 mm

90 mm

64 mm

Din rail mounting guide EN50022

Attacco a guida DIN EN50022

Memory Card  USB

(optional) 

Cod. 2100.30.013

24 23 22

24...230V

AC/DC

B (+)

RS485

CT

PT100

TC

NI100 A\V

PTC NTC

A (-) DO2

(PNP)

DI2

(PNP)

DI1

(PNP)

+V

21 20 19

1

NO C

Q1

Q2

Q3

NC NO

NO 0V (PNP)

DO1 AO1

V/mA

C

C

NC

2

3

4

5

6

7

8

9 10 11 12

18 17 16 15 14 13

DRR244

FNC

SET

C1

C2 A1 A2 A3 TUN MAN REM

Electrical wirings

This controller has been designed and manufactured in conformity to Low Voltage Directive 2006/95/

EC, 2014/35/EU (LVD) and EMC Directive 2004/108/EC, 2014/30/EU (EMC). For installation in industrial 

environments please observe following safety guidelines:

•  Separate control line from power wires.

•  Avoid proximity of remote control switches, electromagnetic contactors, powerful engines.

•  Avoid proximity of power groups, especially those with phase control.

•  It is strongly recommended to install adequate mains filter on power supply of the machine where 

the controller is installed, particularly if supplied 230Vac.

  The controller is designed and conceived to be incorporated into other machines, therefore 

CE marking on the controller does not exempt the manufacturer of machines from safety and 

conformity requirements applying to the machine itself.

•  Wiring of pins: use crimped tube terminals or flexible/rigid copper wire with diameter 0.2 to 2.5 

mm2 (min. AWG28, max. AWG12, operating temperature: min. 70°C). Cable stripping lenght 7 to 8 

mm.

Содержание DRR244

Страница 1: ...DRR244 Controller Regolatore r gulateur User manual Manuale d uso Manuel utilisateur...

Страница 2: ...conceived for applications related to nuclear power plants weapon systems flight control mass transportation systems Only qualified personnel should be allowed to use device and or service it and only...

Страница 3: ...shielded cables and using separate conduits or ducts is recommended Attach a surge suppressor or noise filter to peripheral devices that generate noise in particular motors transformers solenoids mag...

Страница 4: ...0 60 mV Pot Input 1 150 K CT 50 mA Tolerance 25 C 0 2 1 digit on F s for thermocou ple thermoresistance and V mA Cold junction accuracy 0 1 C C Impedence 0 10 V Ri 110 K 0 20 mA Ri 5 0 40 mV Ri 1 M R...

Страница 5: ...3 DRR244 FNC SET C1 C2 A1 A2 A3 TUN MAN REM 5 Electrical wirings This controller has been designed and manufactured in conformity to Low Voltage Directive 2006 95 EC 2014 35 EU LVD and EMC Directive 2...

Страница 6: ...at one side only AI1 PT NI100 Shield Schermo Rosso Red Bianco White Rosso Red 13 14 15 For thermoresistances PT100 Ni100 For the three wire connection use wires with the same section For the two wire...

Страница 7: ...ons 5 1 f Digital output 0V DO1 PNP DO2 PNP 9 10 19 Digital output PNP including SSR for command or alarm Range 12 VDC 25 mA or 24 VDC 15mA selectable by parameter 282 v out 5 1 g Analogue output AO1...

Страница 8: ...ameter value being inserted 6 1 Meaning of Status Lights Led 3 C1 ON when the command output 1 is active In versions with single analog input it is ON when the valve is opening In the versions with tw...

Отзывы: