8 - DRR244 - 

User manual

Model Identification

The DRR244 controller provides the following model:

Power supply 24..230 VAC/VDC ±15% 50/60 Hz – 9 Watt/VA

DRR244-13ABC-T 1 analogue input + 2 relays 5 A + 1 relay 2 A + 2 SSR + 2 D.I. + 1 analogue output 

V/mA + RS485 + CT

Technical Data

3.1 

General Features

Displays

4 digits 0,52’’, 5 digits 0,30’’

Operating temperature

Temperature: 0-45° C -Humidity 35..95 uR%

Max. altitude: 2000m

Sealing

IP20 box

Material

Box: Polycarbonate self-extinguishing;

Front panel: Polyamide self-extinguishing

Weight

Approx. 210 g

3.2 

Hardware Features

Analogue inputs

AI1

Configurable via software.

Input

: Thermocouple type K, S, R, 

J,T,E,N,B.

Automatic compensation of cold 

junction from -25..85° C.

Thermoresistances

: PT100, PT500, 

PT1000, Ni100, PTC 1K, NTC 10K (β 

3435K)

Input V/mA

: 0-1 V, 0-5 V, 0-10 V, 0-20 o 

4-20 mA, 0-60 mV.

Pot. Input

: 1...150 KΩ.

CT

: 50 mA.

Tolerance (25° C)

± 0.2% ±1 digit (on F.s.) for thermocou-

ple, thermoresistance and V/mA.

Cold junction accuracy 0.1° C/°C.

Impedence

:

0-10 V

: Ri>110 KΩ

0-20 mA

: Ri<5 Ω

0-40 mV

: Ri>1 MΩ

Relay outputs

Configurable as command and alarm 

output.

Contacts:

Q1, Q2: 5 A - 250 VAC for resistive load.

Q3: 2 A - 250 VAC for resistive load.

SSR outputs

Configurable as command and alarm 

output.

12/24 V, 25 mA.

Analogue output

Configurable as command

and alarm output or as retrasmission of 

process / setpoints.

Configurable:

0-10 V

 with 40000 /-0.2% (on 

F.s.)

4-20 mA

 con 40000 /-0.2% (on 

F.s.)

Power-supply

Extended power-supply 24..230 VAC/

VDC ±15% 50/60 Hz

Consumption: 

9 Watt/VA

3.3 

Software Features

Regulation algorithms 

ON-OFF with hysteresis.

P, PI, PID, PD with proportional time

Proportional band

0..9999°C o °F 

Integral time

0,0..999,9 sec (0 excludes)

Derivative time

0,0..999,9 sec (0 excludes)

Controller functions

Manual or automatic Tuning, selectable alarm, protection of command 

and alarm setpoints.

Содержание DRR244

Страница 1: ...DRR244 Controller Regolatore r gulateur User manual Manuale d uso Manuel utilisateur...

Страница 2: ...conceived for applications related to nuclear power plants weapon systems flight control mass transportation systems Only qualified personnel should be allowed to use device and or service it and only...

Страница 3: ...shielded cables and using separate conduits or ducts is recommended Attach a surge suppressor or noise filter to peripheral devices that generate noise in particular motors transformers solenoids mag...

Страница 4: ...0 60 mV Pot Input 1 150 K CT 50 mA Tolerance 25 C 0 2 1 digit on F s for thermocou ple thermoresistance and V mA Cold junction accuracy 0 1 C C Impedence 0 10 V Ri 110 K 0 20 mA Ri 5 0 40 mV Ri 1 M R...

Страница 5: ...3 DRR244 FNC SET C1 C2 A1 A2 A3 TUN MAN REM 5 Electrical wirings This controller has been designed and manufactured in conformity to Low Voltage Directive 2006 95 EC 2014 35 EU LVD and EMC Directive 2...

Страница 6: ...at one side only AI1 PT NI100 Shield Schermo Rosso Red Bianco White Rosso Red 13 14 15 For thermoresistances PT100 Ni100 For the three wire connection use wires with the same section For the two wire...

Страница 7: ...ons 5 1 f Digital output 0V DO1 PNP DO2 PNP 9 10 19 Digital output PNP including SSR for command or alarm Range 12 VDC 25 mA or 24 VDC 15mA selectable by parameter 282 v out 5 1 g Analogue output AO1...

Страница 8: ...ameter value being inserted 6 1 Meaning of Status Lights Led 3 C1 ON when the command output 1 is active In versions with single analog input it is ON when the valve is opening In the versions with tw...

Отзывы: