36 - CNV580 - User manual
7.3.c
Analog Input
•
Enable Analog Input
: enable/desable operation of analog input AI1
•
Over Limit
: enable/desable possibility for the analog input to exceed
AI Lower/Upper limits
•
AI Lower limit (+/- 2000000)
: lower limit of analog input used for for
linearization of input 4-20 mA. This is the value associated to 4 mA
•
AI Upper limit (+/- 2000000)
: upper limit of analog input used for
linearization of input 4-20 mA. This is the value associated to 20 mA
•
Calibration Offset (+/- 1000)
: Offset calibration. This value can be
added or subtracted to value of input AI1.
-1000..+1000 [digit].
Default
0.
•
Calibration Gain (+/- 1000)
: Gain calibration. This value can be
multiplied for process value to calibrate it. Example to correct a scale
0...1000°C showing 0...1010°C, set this parameter to -1.0
-1000 (100.0%)...+1000 (+100.0%),
Default
: 0.0.
•
Conversion Filter (1 – 30)
: Filter on the reading of analogue input. It
increases stability of reading. It indicates number of sampling values
to consider for calculation of process value
1...30. (
Default
: 10)