18 - CNV580 - User manual
4.e
Examples of connection for AI1 input
4...20mA
P :0...100mbar Pmax :3bar T :0..70°C
OUT
: 4...20mA
IN :9...33V DC
3
5
For 0/4..20 mA normalized current signals with
two
wire sensor
.
Respect the polarity:
5 = Sensor output
3 = Power supply (12...34 V DC)
In the picture: pressure sensor.
4.f
Isolated digital inputs
6
DI1
0V
8
DI2
7
12..24 V AC / DC
PNP inputs (to activate input, connect a positive
signal to corresponding pin)
1,5 kV galvanic isolation