16 - CNV580 - User manual
• It is strongly recommended to install adequate mains filter on power
supply of the machine where the controller is installed, particularly
if supplied 230 VAC. The device is designed and conceived to be
incorporated into other machines, therefore CE marking on the
controller does not exempt the manufacturer of machines from safety
and conformity requirements applying to the machine itself.
• Wiring device, use crimped tube terminals or flexible/rigid copper
wire with diameter 0.14 to 1.5 mm
2
(min. AWG28, max. AWG16). Cable
stripping lenght is 7 mm.
• It is possible to connect on a single terminal two wires with same
diameter comprised between 0.14 and 0.75mm
2
.
4.a
Power supply
1
+
-
2
SUPPLY
12...24 V AC / DC ± 15%
4.b
Digital output PNP
3
+V
Q1-
4
LOAD
Q1-: PNP output max. 30 mA.