38
ATR 621 - User manual
32
Special
Functions
Enables simple thermoregulator function and manual setting of output
percentage.
(Disabled) No function available. >
Default
.
(Thermoregulator) Enables simple thermoregulator function.
(Manual) Enables manual mode.
(Thermoregulator and Manual) Enables both simple thermore-
gulator and manual function.
33
Hold
Function
Enables “Hold” function; allows to hold the cycle and modify setpoint by
keyboard. The same function
NOT
have to be enabled on Par. 27
.
(Disabled) “Hold” function disabled. >
Default
.
(Enabled) “Hold” function enabled.
34
Cycles
Available
Selects number of available cycles.
1…15
cycles. >
Default
: 15.
35
Block Programming Cycles
Selects number of cycles that the user cannot modify, to avoid wrong
progamming. Ex.: selecting 3 the programming of fi rst 3 cycles is locked.
0…15
locked cycles. >
Default
: 0.
36
Waiting Time Step End
Selects time for step end waiting in hh.mm.
00.00
Step end waiting excluded
00.01…24.00
hh.mm. >
Default
: 01.00.
37
Max. Gap Step End
Selects max. gap for step end waiting activation. When the diff erence
between setpoint and process is lower than this parameter, controller
switch to the next step (also without waiting time programmed into
parameter 36
0…200
[digit
4
] (degrees.tenths for temperature sensors). >
Default
: 5.