ATR243 - User manual -
39
55
c.frn.
Conversion Frequency
Sampling frequency of analogue / digital converter.
NB
: Increasing the conversion speed will slow down reading stability (example: for
fast transients, as pressure, it is advisable to increase sampling frequency)
242H.
242 Hz (Maximum speed conversion)
123H.
123 Hz
62 H.
62 Hz
50 H.
50 Hz
39 H.
39 Hz
33.2H.
33.2 Hz
19.6H.
19.6 Hz
16.7H.
16.7 Hz (
Default
) Ideal for filtering noises 50 / 60 Hz
12.5H.
12.5 Hz
10 H.
10 Hz
8.33H.
8.33 Hz
6.25H.
6.25 Hz
4.17H.
4.17 Hz (Minimum speed conversion)
56
u.FLt.
Visualization Filter
Slow down the refresh of display, to simplify reading
dis.
Disabled with pitchfork (max. speed of display update)
Default
.
fi.or.
First order filter with pitchfork
2. s.m.
2 Samples Mean
3. s.m.
3 Samples Mean
4. s.m.
4 Samples Mean
5. s.m.
5 Samples Mean
6. s.m.
6 Samples Mean
7. s.m.
7 Samples Mean
8. s.m.
8 Samples Mean
9. s.m.
9 Samples Mean
10.s.m.
10 Samples Mean (Maximum slow down of display update)
nuLL
Disabled without pitchfork
f.o. 2
First order filter
57
tune
Tune
Tuning type selection. (See paragraph 7.2)
diS.
Disabled (
Default
)
Auto
Automatic (P.I.D. parameters are calculated at activation and at change of
set point)
Man.
Manual (launch by keyboard or digital IN)
sYnc.
Synchronized [see word modbus 1025 (
only ATR243-21ABC-T
)]
58
s.dtu.
Setpoint Deviation Tune
Select the deviation from the command setpoint for the threshold used by
autotuning to calculate the P.I.D. parameters