32 -
ATR243 - User manual
8
Latc.
Latch On Function
Automatic setting of limits for linear inputs and potentiometers (see paragraph 7.9)
dis.
Disabled (
Default
)
std.
Standard
u.0st.
Virtual zero stored
u.0in
Virtual zero initialized
dYn.L
Allows to surpass lower and upper limits if on input there are values out of
0/4…20mA or 0…10V.
9
o.cAL.
Offset Calibration
Value added / subtracted to process visualization (usually correcting the value of
environment temperature)
-999…+1000
[digit
5
] for linear sensors and potentiometers.
-200.0…+100.0
(degrees.tenths for temperature sensors),
Default
0.0.
10
G.cAL.
Gain Calibration
Percentage value that is multiplied for the process value (allows to calibrated the
working point)
-99.9%…+100.0% (
Default
= 0.0)
ex: to correct the range from 0...1000°C showing 0...1010°C, set the parameter to -1.0.
11
Act.t.
Action type
Regulation type
Heat
Heating (N.O.) (
Default
)
cooL
Cooling (N.C.)
H.o.o.S.
Lock command above SPV. Example: command output disabled when
reaching setpoint, also with P.I.D. value different from 0
12
c. re.
Command Reset
Type of reset for state of command contact (always automatic in P.I.D. functioning)
are.
Automatic reset (
Default
)
mre.
Manual reset
mre.s.
Manual reset stored (keeps relay status also after an eventual power failure)
13
c. S.e.
Command State Error
State of contact for command output in case of error
c.o.
Open contact (
Default
)
c.c.
Closed contact
14
c. Ld.
Command Led
State of the OUT1 led corresponding to the relevant contact
c.o.
ON with open contact
c.c.
ON with closed contact (
Default
)