20 -
ATR243 - User manual
Updating Memory Card
To update the memory card values, follow the procedure described on first mode, setting
display 2 to
----
so as not to load the parameters on controller
1
.
Enter configuration and
change at least one parameter
.
Exit configuration. Changes are stored automatically.
7.9 Latch-on function
For use with input
Pot.1
(potentiometer 6 KΩ) and
Pot.2
(potentiometer 150 KΩ) and with
linear input (0…10 V, 0...40 mV, 0/4…20 mA), it is possible to associate start value of the
scale (parameter 6
LoL.i
) to the minimum position of the sensor and value of end scale
(parameter 7
uP.L.i
) to the maximum position of the sensor (parameter 8
Latc.
configured
as
Std.
).
It is also possible to fix the point in which the controller will display 0 (however keeping
the scale range between
LoL.i
and
uP.L.i
) using the
“virtual zero”
option by setting
u.OSt.
or
u.Oin.
in parameter 8
Latc
.
If you set
u.Oin.
the virtual zero will reset after each activation of the tool; if you set
u.OSt.
the virtual zero remains fixed once tuned.
Selecting “
dYn.L
” (dynamic limits) it is possible to surpass lower and upper limits if on
input there are values out of 0/4…20mA or 0…10V .
To enable the LATCH ON function select chosen configuration for parameter
LAtc
2
.
For the calibration procedure refer to the following table:
Press
Display
Do
1
+
simultaneously
Exit parameters configura-
tion. Display 2 shows the
writing
LAtc
.
Place the sensor on minimum
operating value (associated
with
LoL.i.
).
2
Set the value on minimum.
Display shows
Low
.
Place the sensor on maximum
operating value (associated
with
upL.i.
).
3
Set the value to maximum.
The display shows
HiGH
.
To exit standard procedure
press
SET
. For
“virtual zero”
settings place the sensor on
the zero point.
4
SET
Set the virtual zero value.
Display shows
uirt
.
NB
: For selection of
u.0in.
the procedure in point 4
should be followed on each
re-activation.
To exit procedure press
SET
.
1
If on activation the controller does not display memo it means no data have been saved on the memory
card, but it is possible to update values.
2
The tuning procedure starts by exiting the configuration after changing the parameter.