35
/124
EN
35
/60
This manual belongs to PIUSI S.p.A. The reproduction of all or parts is prohibited.
CUBE
EN (translated from Italian)
16 START-UP
FOREWORD
For a correct start-up of CUBE B.SMART, in addition to the activation of
apps and webapps, it is necessary to perform some simple operations.
POWER
SUPPLY
Once the electrical connections have been made, it is possible to power the
CUBE B.SMART by means of the main switch that the installer must arrange on
the upstream line.
The system will be turned on when the backlit LCD screen installed on the front
panel is activated. Even if you remove the nozzle from its housing, the pump will
NOT start, as it is not enabled by the B.SMART system.
PUMP
WETTING
CUBE B.SMART is equipped with a self-priming pump that facilitates the
first start-up activities. It is therefore not necessary for the suction pipe to be
completely filled with diesel for starting up. For rapid priming, particularly in
installations with a significant height difference between the pump and the
tank, it is nevertheless important that the pump is “wet”, i.e. that a minimum
quantity of diesel is present inside the impeller chamber. The pump is delivered
properly “wet” and ready for use. If, however, the installer believes that the pump
is completely dry, for example due to prolonged storage, he must wet it as he
deems most appropriate.
16.1 FIRST PRIMING
For priming the pump:
- Pull the nozzle out of its housing
- ACTIVATE THE DELIVERY (VIA APP, WEBAPP OR I-BUTTON KEY)
- Raise the control lever
- The pump will start immediately and continue running indefinitely until the
control lever is turned to the OFF position
POSITION
ON
POSITION
OFF
- Operate the lever of the automatic nozzle, keeping the spout inside a
suitable container or the suction tank itself. Initially, air will come out of the
nozzle and after a certain time the DIESEL will start to flow out.
IMPORTANT
The first priming of the pump must be carried out by competent personnel
who shall be present at all stages. If the air-only delivery phase should take
longer than a couple of minutes, STOP the PUMP and check that:
• The pump does not run completely dry, but is at least “wet” with diesel.
• The suction pipe guarantees total absence of air infiltration and is
completely immersed.
• The filters are not clogged.
• The suction and/or discharge pipes are not blocked.
• The installation (height difference, diameter and pipe length) complies
with the limits described in chapter 14.
• The shut-off valve is closed.
Continue dispensing until the flow is constant and free of air. Set the control
lever to the OFF position: The pump stops. Re-position the nozzle in its
housing.
Содержание CUBE B.SMART
Страница 1: ...CUBE Bulletin M0546 EN_01 Installation use and maintenance EN ...
Страница 2: ...Installation use and maintenance M0546 2 60 Bulletin M0546 ENGLISH ...
Страница 56: ...Installation use and maintenance M0546 56 60 24 EXPLODED VIEWS ...
Страница 58: ...Installation use and maintenance M0546 58 60 note ...
Страница 59: ......