12 INSTALLATION
CUBE MC can be installed outside. Nevertheless, it is advisable to locate it
under the shelterof a roof to ensure the dispenser’s longevity and provide
greater comfort during refuelling inthe event of bad weather. The installation
of the dispenser must be carried out by skilledpersonnel and performed ac-
cording to the instructions provided in this chapter.Whenever CUBE MC is not
installed under cover, a “display cover” is provided to protected thedisplay and
keyboard.
WARNING
Authorised
installation per-
sonnel
All installations must be carried out by authorised and competent personnel
only. Authorised persons must
- install the system in dry and well-ventilated place;
- ensure the correct installation of equipment required for the correct func-
tioning of the pump;
- only use accessories that have been supplied with the system.
ATTENTION
The use of accessories that are unsuitable and were not provided with the
system is strictly prohibited. Piusi S.p.A. accepts no responsibility for dam-
age to persons, property or the environment caused by failure to comply
with this requirement.
THE DISPENSING SYSTEM IS FOR PROFESSIONAL USE ONLY.
As per the current legislation, the dispensing system must be used n prem-
ises that are sufficiently well-lit.
The dispensing system has been specifically designed for use in a dry place.
If installed outside, an adequate protective covering must be provided.
Motors are not explosion-proof. DO NOT install CUBE MC in places with
danger of explosion.
12.1 POSITIONING
The positioning of the SELF SERVICE must be such that it is possible to:-
Easily remove the panels to access the inner components when necessary.-
Observe the distances and maximum differences in level between the station
and the tank.- Securely fasten the casing to the ground on a horizontal sur-
face. Station positioning determines the following parameters, which distin-
guish each installation:
Hp: Priming height
Ls: Total length of the suction pipe - from the foot valve to the
station(expressed in metres)
To ensure correct station operation, the following limitations must always be
kept to:
Hp max: not over 3 metres
LS max: not over 15 metres