AFP 300/400 I
NSTALLATION
A
ND
P
ROGRAMMING
M
ANUAL
P
AGE
7
C
OPYRIGHT
© 2000, N
OTIFIER
I
NERTIA
P
TY
L
TD
Compatible Annunciators
ACM-16AT -
Contains 16 red alarm and 16 yellow LEDs, and a local piezo sounder,
Includes 16 switches for control panel functions.
AEM-16AT -
Expands the ACM-16AT by 16 system points per unit, up to a maximum of 64
points per address.
ACM-32A -
Contains 32 red alarm LEDs, and a local piezo sounder with silence/acknowledge
switch.
AEM-32A -
Expands the ACM-32A by 32 points
ACM-8R-
Provides eight Clean contact (Form-C) relays with 5A contacts
LDM-32-
Provides 32 Led driver outputs for connection to a custom graphic Mimic.
Programmable for 32 alarm only outputs, or 16 alarm and 16 fault outputs.
LDM-E32-
Expands the LDM-32 by 32 points up to a maximum of 64 points.
LDM-R32-
Converts the open collector outputs of an LDM-32 or LDM-E32 to Form-A
(normally open) contacts.
LCD-80-
Alphanumeric display Mimic Panel
Initial Installation Tasks
Check AC Power –
Apply AC power to the MPS-400, but do not connect batteries at this time.
Silence the audible fault sounder by pushing the Acknowledge switch on the Keypad.
The Panel should indicate:
The Green AC power LED on
System Fault indicator because of no batteries
The yellow fault indicator may come on after 10 seconds.
Program the AFP-400 (See Programming)
Connect the Batteries
Carry out common fault finding techniques (Page 19)
Test the System.