P
AGE
32
AFP 300/400 I
NSTALLATION
A
ND
P
ROGRAMMING
M
ANUAL
C
OPYRIGHT
© 2000, N
OTIFIER
I
NERTIA
P
TY
L
TD
System Check Function
When finished programming use the Check option to search the program entries for possible
errors. From the program mode screen, select <8> to check the system program, the screen will
now show:
When Check completed the screen will show possible errors in the program:
Output points mapped to a zone without a mapped input
A zone with mapped inputs without mapped outputs
Releasing Zone Inputs (R0-R9) with no RELEASE CKT outputs mapped to them.
R0-R9 Inputs not mapped to MAN RELEASE.
If the Check options detects errors, return to Point Programming and correct the errors.
Status Change
Press the <
ENTER>
key to enter programming mode.
Technical Note: When programming mode is entered the ACS EIA-485 output is disabled.
Press <
1
> The system displays the following screen.
Press <
ENTER
> The screen now display’s:
The Status change screen allows you to change control panel operating parameters. These
operating parameters do not affect the basic configuration or the control program settings.
The control panel will return to standard mode whenever the keypad is inactive for more than 2
minutes.
PRORAM CHECK OK.
RE-TEST PANEL NOW
11:10A Wed 05/07/00
STATUS CHANGE PRESS: 1=ISOL/DEIS 2=SENSITIV
3=CLR VER 4=CLR HIST 5=TIME 6=WALK TEST
1=PROGRAMMING 2=READ STATUS ENTRY
(ESCAPE TO ABORT)
ENTER
PASSWORD THEN ENTER, OR PRESS ENTER
FOR SYSTEM STAT CHANGE <ESC>
*****
Technical Manuals Online! - http://www.tech-man.com