P
AGE
40
AFP 300/400 I
NSTALLATION
A
ND
P
ROGRAMMING
M
ANUAL
C
OPYRIGHT
© 2000, N
OTIFIER
I
NERTIA
P
TY
L
TD
Sensitivity Levels- Autoprogram Default Tables:
Photo Optical Detectors
Description
*Indicates the Default level setting,
Between 1 and 9.
Level
Alarm
Pre-alarm
0
Not Used
No Pre-Alarm
1
0.67%
Auto
2
1.67%
0.50%
3
2.50%
0.67%
4
3.33%
1.00%
5
4.16%
1.67%
6
5.00%
2.50%
7
5.83%
3.33%
8*
6.66%
4.16%
9
7.83%
5.00%
Ionisation Detectors
Description
*
Indicates the Default level setting,
Between 1 and 9.
Level
Alarm
Pre-alarm
0
Not Used
No Pre-Alarm
1
1.67%
Auto
2
2.50%
1.33%
3
3.33%
1.83%
4
4.16%
2.50%
5
5.00%
3.33%
6*
5.83%
4.16%
7
6.66%
5.00%
8
7.49%
5.83%
9
8.33%
6.66%
Laser Detectors
Description
*
Indicates the Default level setting,
Between 1 and 9.
Level
Alarm
Pre-alarm
0
Not Used
No Pre-Alarm
1
0.10%
Auto
2
0.17%
0.07%
3
0.33%
0.10%
4
0.67%
0.17%
5
1.00%
0.33%
6*
1.33%
0.67%
7
1.67%
1.17%
8
2.50%
1.33%
9
3.33%
1.67%
Multi Sensor Detectors
Description
*
Indicates the Default level setting,
Between 1 and 9.
Level
Alarm
Pre-alarm
0
Not Used
No Pre-Alarm
1
2.50%
Auto
2
2.50%
1.67%
3
3.33%
1.67%
4
3.33%
3.33%
5*
6.66%
3.33%
6
9.99%
6.66%
7
9.99%
6.66%
8
13.32%
9.99%
9
13.32%
9.99%
Note:
If Multi-Detector mode is selected then the group detector sensitivity can be reduced down to
.58% of the original alarm setting.
For additional programming assistance please contact your supplier.
Technical Manuals Online! - http://www.tech-man.com