XP-5M & XP-5C Modules
The XP-5 Control and XP-5 Monitor modules are 5 separate modules and addresses mounted
on one circuit card, the address is chosen by one rotary switch and one slide switch.
The rotary switch selects the address in increments of ten, and the slide switch selects either 0
or 5. Eg; address 52- the rotary switch will be 5, and the slide switch will be 0.
Address 52 will be the third point on the XP-5 card.
The wiring of both the XP-5C and XP-5M are wired exactly as the CMX-2 and MMX-101
devices, the only difference being that they share the same loop connection.
Note: Each output on the XP-5C is selectable via a switch.
Monitored output = Switch Depressed (Above Line)
Monitored output circuits are to be wired as per a CMX-2
and connected to the XP5-C as shown.
Address Sw1-5 set
ON,
For Future Use,
Set SW1-5 Off