86
Outdoor check function
N
Display
Remark
00
Normal display
Display running frequency, running state or malfunction
code
01
Indoor unit capacity demand code
Actual data*HP*10
If capacity demand code is higher than 99, the digital display
tube will show single digit and tens digit. (For example, the
digital display tube show “5.0”,it means the capacity demand
is 15. the digital display tube show “60”,it means the
capacity demand is 6.0)
02
Amendatory capacity demand code
03
The frequency after the capacity requirement
transfer
04
The frequency after the frequency limit
05
The frequency of sending to 341 chip
06
Indoor unit evaporator outlet temp.(heating T2
,
cooling T2B)
If the temp. is lower than 0 degree, the digital display tube
will show “0”.If the temp. is higher than 70 degree, the digital
display tube will show “70”.
07
Condenser pipe temp.(T3)
If the temp. is lower than -9 degree, the digital display tube
will show “-9”.If the temp. is higher than 70 degree, the
digital display tube will show “70”. If the indoor unit is not
connected, the digital display tube will show: “――”
08
Outdoor ambient temp.(T4)
09
Compressor discharge temp.(T5)
The display value is between 13~129 degree. If the temp. is
lower than 13 degree, the digital display tube will show
“13”.If the temp. is higher than 99 degree, the digital display
tube will show single digit and tens digit. (For example, the
digital display tube show “0.5”,it means the compressor
discharge temp. is 105 degree. the digital display tube show
“1.6”,it means the compressor discharge temp. is 116
degree)
10
AD value of current
The display value is hex number.
11
AD value of voltage
12
Indoor unit running mode code
Off:0, Fan only 1,Cooling:2, Heating:3
13
Outdoor unit running mode code
Off:0, Fan only 1,Cooling:2, Heating:3, Forced cooling:4
14
EXV open angle
Actual data/4.
If the value is higher than 99, the digital display tube will
show single digit and tens digit.
For example, the digital display tube show “2.0”,it means the
EXV open angle is 120×4=480p.)
Содержание YN009GMFI22RPD
Страница 8: ...5 2 2 Part names of Indoor Outdoor units Ceiling Cassette Unit ...
Страница 9: ...6 Ducted Concealed Units ...
Страница 10: ...7 Floor Console Units ...
Страница 11: ...8 Ceiling Floor Units ...
Страница 24: ...21 Console Units 16 Drain pipe 195 Hanging arm Unit mm 700 600 210 ...
Страница 28: ...25 Console Unit Ceiling floor Units ...
Страница 32: ...29 FB009GMFILCFHD FB012GMFILCFHD UB018GMFILCFHD ...
Страница 33: ...30 UB018GMFILCFHD CB036GMFILCFHD CB048GMFILCFHD ...
Страница 34: ...31 RB036GMFILCFHD RB048GMFILCFHD ...
Страница 35: ...32 UB036GMFILCFHD UB048GMFILCFHD ...
Страница 36: ...33 UB036GMFILCFHD UB048GMFILCFHD ...
Страница 37: ...34 6 2 Outdoor Unit YN009GMFI22RPD YN012GMFI22RPD ...
Страница 38: ...35 YN018GMFI22RPD ...
Страница 39: ...36 YN024GMFI22RPD ...
Страница 40: ...37 YN036GMFI17RUD ...
Страница 41: ...38 YN048GMFI17RUD ...
Страница 42: ...39 Outdoor Controller Set of For YN009GMFI22RPD YN012GMFI22RPD For YN018GMFI22RPD ...
Страница 44: ...41 RB009GMFILCFHD Code 0 Code 1 Code 2 Code 3 Code 4 ...
Страница 45: ...42 RB012GMFILCFHD Code 0 Code 1 Code 2 Code 3 Code 4 ...
Страница 46: ...43 RB018GMFILCFHD Code 0 Code 1 Code 2 Code 3 Code 4 ...
Страница 47: ...44 RB024GMFILCFHD Code 0 Code 1 Code 2 Code 3 Code 4 ...
Страница 48: ...45 RB036GMFILCFHD Code 0 Code 1 Code 2 Code 3 Code 4 ...
Страница 49: ...46 RB048GMFILCFHD Code 0 Code 1 Code 2 Code 3 Code 4 ...
Страница 58: ...55 12 Field Wiring 36 000 and 48 000 BTU Models ...
Страница 100: ...97 P U P V ...
Страница 101: ...98 P W P N ...
Страница 116: ...113 4 Remove the evaporator support board 5 Screw off the fixing screws to remove the evaporator 4 screws 1 screw ...