69
2. Pump drainage mode
2.1 Disconnect the plug of water level switch,
remove the cover of water test hole and slowly
infuse about 2000ml water through the water
test hole, be sure that the water will not touch
the motor of drainage pump.
2.2 Power on and let the air conditioner
operate for cooling. Check operation status
of drainage pump, and then connect the
plug of water level switch, check the
operation sound of water pump and
observe whether the water can discharge
through the transparent hard pipe at
drainage outlet. (In light of the length of
drainage pipe, water shall be discharged
about 1 minute delayed)
2.3 Stop the operation of air conditioner, power
off the power supply and put the cover of
water test hole back to the original place.
a. After stopped the air conditioner 3 minutes,
check whether there is anything abnormal.
If drainage pipes have not been distributed
properly, over back-flow water shall cause
the flashing of alarm indicator at
remote-controlled receiving board and
even water shall run over the water
collector.
b. Continuously infusing water until water
level alarmed, check whether the drainage
pump could discharge water at once. If
water level does not decline under warning
water level 3 minutes later, it shall cause
shutdown of unit. When this situation
happens, the normal startup only can be
recovered by turning down power supply
and eliminating accumulated water.
Note:
Drain plug at the main water-containing
plate is used for eliminating accumulated water
in water-containing plate when maintaining air
conditioner fault. During normal operation, the
plug shall be filled in to prevent leakage.
12.5.4 Insulation work of drainage pipe
Refer the introduction to the insulation
engineering parts.
12.6 Vacuum Drying and Leakage
Checking
12.6.1 Purpose of vacuum drying
Eliminating moisture in system to prevent
the phenomena of ice-blockage and copper
oxidation.
Содержание YN009GMFI22RPD
Страница 8: ...5 2 2 Part names of Indoor Outdoor units Ceiling Cassette Unit ...
Страница 9: ...6 Ducted Concealed Units ...
Страница 10: ...7 Floor Console Units ...
Страница 11: ...8 Ceiling Floor Units ...
Страница 24: ...21 Console Units 16 Drain pipe 195 Hanging arm Unit mm 700 600 210 ...
Страница 28: ...25 Console Unit Ceiling floor Units ...
Страница 32: ...29 FB009GMFILCFHD FB012GMFILCFHD UB018GMFILCFHD ...
Страница 33: ...30 UB018GMFILCFHD CB036GMFILCFHD CB048GMFILCFHD ...
Страница 34: ...31 RB036GMFILCFHD RB048GMFILCFHD ...
Страница 35: ...32 UB036GMFILCFHD UB048GMFILCFHD ...
Страница 36: ...33 UB036GMFILCFHD UB048GMFILCFHD ...
Страница 37: ...34 6 2 Outdoor Unit YN009GMFI22RPD YN012GMFI22RPD ...
Страница 38: ...35 YN018GMFI22RPD ...
Страница 39: ...36 YN024GMFI22RPD ...
Страница 40: ...37 YN036GMFI17RUD ...
Страница 41: ...38 YN048GMFI17RUD ...
Страница 42: ...39 Outdoor Controller Set of For YN009GMFI22RPD YN012GMFI22RPD For YN018GMFI22RPD ...
Страница 44: ...41 RB009GMFILCFHD Code 0 Code 1 Code 2 Code 3 Code 4 ...
Страница 45: ...42 RB012GMFILCFHD Code 0 Code 1 Code 2 Code 3 Code 4 ...
Страница 46: ...43 RB018GMFILCFHD Code 0 Code 1 Code 2 Code 3 Code 4 ...
Страница 47: ...44 RB024GMFILCFHD Code 0 Code 1 Code 2 Code 3 Code 4 ...
Страница 48: ...45 RB036GMFILCFHD Code 0 Code 1 Code 2 Code 3 Code 4 ...
Страница 49: ...46 RB048GMFILCFHD Code 0 Code 1 Code 2 Code 3 Code 4 ...
Страница 58: ...55 12 Field Wiring 36 000 and 48 000 BTU Models ...
Страница 100: ...97 P U P V ...
Страница 101: ...98 P W P N ...
Страница 116: ...113 4 Remove the evaporator support board 5 Screw off the fixing screws to remove the evaporator 4 screws 1 screw ...