107
3. IPM continuity check
Turn off the power, let the large capacity electrolytic capacitors discharge completely, and dismount the IPM. Use a digital
tester to measure the resistance between P and UVWN; UVW and N.
Digital tester
Normal resistance value
Digital tester
Normal resistance value
(+)Red
(-)Black
∞
(Several MΩ)
(+)Red
(-)Black
∞
(Several MΩ)
P
N
U
N
U
V
V
W
W
(+)Red
4: Pressure on Service Port
Cooling chart:
COOLING MODE
℉
(
℃
)
Indoor
Temp.
Outdoor temp.
75
(
23.89
)
85
(
29.44
)
95
(
35
)
105
(
40.56
)
115
(
46.11
)
BAR
70
8.2
7.8
8.1
8.6
10.1
BAR
75
8.6
8.3
8.7
9.1
10.7
BAR
80
9.3
8.9
9.1
9.6
11.2
PSI
70
119
113
117
125
147
PSI
75
124
120
126
132
155
PSI
80
135
129
132
140
162
MPA
70
0.82
0.78
0.81
0.86
1.01
MPA
75
0.86
0.83
0.87
0.91
1.07
MPA
80
0.93
0.89
0.91
0.96
1.12
0.0
2.0
4.0
6.0
8.0
10.0
12.0
75
(
23.89
)
85
(
29.44
)
95
(
35
)
105
(
40.56
)
115
(
46.11
)
70
75
80
Pressure (bar)
Outdoor temp.
Содержание YN009GMFI22RPD
Страница 8: ...5 2 2 Part names of Indoor Outdoor units Ceiling Cassette Unit ...
Страница 9: ...6 Ducted Concealed Units ...
Страница 10: ...7 Floor Console Units ...
Страница 11: ...8 Ceiling Floor Units ...
Страница 24: ...21 Console Units 16 Drain pipe 195 Hanging arm Unit mm 700 600 210 ...
Страница 28: ...25 Console Unit Ceiling floor Units ...
Страница 32: ...29 FB009GMFILCFHD FB012GMFILCFHD UB018GMFILCFHD ...
Страница 33: ...30 UB018GMFILCFHD CB036GMFILCFHD CB048GMFILCFHD ...
Страница 34: ...31 RB036GMFILCFHD RB048GMFILCFHD ...
Страница 35: ...32 UB036GMFILCFHD UB048GMFILCFHD ...
Страница 36: ...33 UB036GMFILCFHD UB048GMFILCFHD ...
Страница 37: ...34 6 2 Outdoor Unit YN009GMFI22RPD YN012GMFI22RPD ...
Страница 38: ...35 YN018GMFI22RPD ...
Страница 39: ...36 YN024GMFI22RPD ...
Страница 40: ...37 YN036GMFI17RUD ...
Страница 41: ...38 YN048GMFI17RUD ...
Страница 42: ...39 Outdoor Controller Set of For YN009GMFI22RPD YN012GMFI22RPD For YN018GMFI22RPD ...
Страница 44: ...41 RB009GMFILCFHD Code 0 Code 1 Code 2 Code 3 Code 4 ...
Страница 45: ...42 RB012GMFILCFHD Code 0 Code 1 Code 2 Code 3 Code 4 ...
Страница 46: ...43 RB018GMFILCFHD Code 0 Code 1 Code 2 Code 3 Code 4 ...
Страница 47: ...44 RB024GMFILCFHD Code 0 Code 1 Code 2 Code 3 Code 4 ...
Страница 48: ...45 RB036GMFILCFHD Code 0 Code 1 Code 2 Code 3 Code 4 ...
Страница 49: ...46 RB048GMFILCFHD Code 0 Code 1 Code 2 Code 3 Code 4 ...
Страница 58: ...55 12 Field Wiring 36 000 and 48 000 BTU Models ...
Страница 100: ...97 P U P V ...
Страница 101: ...98 P W P N ...
Страница 116: ...113 4 Remove the evaporator support board 5 Screw off the fixing screws to remove the evaporator 4 screws 1 screw ...