63
1/2"
(12.7)
15.4
15.8
5/8"
(15.9)
18.6
19.1
3/4" (19) 22.9
23.3
After flared the pipe, the opening part must
be seal by end cover or adhesive tape to
avoid duct or exogenous impurity come into
the pipe.
7. Drill holes if the pipes need to pass the
wall.
8. According to the field condition to bend the
pipes so that it can pass the wall smoothly.
9. Bind and wrap the wire together with the
insulated pipe if necessary.
10. Set the wall conduit
11. Set the supporter for the pipe.
12. Locate the pipe and fix it by supporter
For horizontal refrigerant pipe, the distance
between supporters should not be exceed
1m.
For vertical refrigerant pipe, the distance
between supporters should not be exceed
1.5m.
13. Connect the pipe to indoor unit and outdoor
unit by using two spanners.
Be sure to use two spanners and proper
torque to fasten the nut, too large torque
will damage the flare, and too small torque
may cause leakage. Refer the following
table for different pipe connection.
Pipe
Diameter
Torque
Sketch map
(kgf.cm)
(N.cm)
1/4" (6.35)
144~176
1420~1720
3/8" (9.52)
333~407
3270~3990
1/2" (12.7)
504~616
4950~6030
5/8" (15.9)
630~770
6180~7540
3/4" (19)
990~1210 9270~11860
12.4.3 Installation for the first time
Air and moisture in the refrigerant system have
undesirable effects as below:
●
Pressure in the system rises.
●
Operating current rises.
●
Cooling or heating efficiency drops.
●
Moisture in the refrigerant circuit may
freeze and block capillary tubing.
●
Water may lead to corrosion of parts in the
refrigerant system.
Therefore, the indoor units and the pipes
between indoor and outdoor units must be leak
tested and evacuated to remove gas and
moisture from the system.
Gas leak check (Soap water method):
Apply soap water or a liquid neutral detergent
on the indoor unit connections or outdoor unit
connections by a soft brush to check for
leakage of the connecting points of the piping. If
bubbles come out, the pipes have leakage.
1. Air purging with vacuum pump
1) Completely tighten the flare nuts of the
indoor and outdoor units, confirm that both
the 2-way and 3-way valves are set to the
closed position.
2) Connect the charge hose with the push pin
of handle lo to the 3-way valves gas service
port..
3) Connect the charge hose of handle hi
connection to the vacuum pump.
4) Fully open the handle Lo of the manifold
valve.
5) Operate the vacuum pump to evacuate.
6) Make evacuation for 30 minutes and check
whether the compound meter indicates
-0.1Mpa (14.5Psi). If the meter does not
indicate -0.1Mpa (14.5Psi) after pumping 30
minutes, it should be pumped 20 minutes
more. If the pressure can’t achieve -0.1Mpa
(14.5Psi) after pumping 50 minutes, please
check if there are some leakage points.
Fully close the handle Lo valve of the
manifold valve and stop the operation of the
Содержание YN009GMFI22RPD
Страница 8: ...5 2 2 Part names of Indoor Outdoor units Ceiling Cassette Unit ...
Страница 9: ...6 Ducted Concealed Units ...
Страница 10: ...7 Floor Console Units ...
Страница 11: ...8 Ceiling Floor Units ...
Страница 24: ...21 Console Units 16 Drain pipe 195 Hanging arm Unit mm 700 600 210 ...
Страница 28: ...25 Console Unit Ceiling floor Units ...
Страница 32: ...29 FB009GMFILCFHD FB012GMFILCFHD UB018GMFILCFHD ...
Страница 33: ...30 UB018GMFILCFHD CB036GMFILCFHD CB048GMFILCFHD ...
Страница 34: ...31 RB036GMFILCFHD RB048GMFILCFHD ...
Страница 35: ...32 UB036GMFILCFHD UB048GMFILCFHD ...
Страница 36: ...33 UB036GMFILCFHD UB048GMFILCFHD ...
Страница 37: ...34 6 2 Outdoor Unit YN009GMFI22RPD YN012GMFI22RPD ...
Страница 38: ...35 YN018GMFI22RPD ...
Страница 39: ...36 YN024GMFI22RPD ...
Страница 40: ...37 YN036GMFI17RUD ...
Страница 41: ...38 YN048GMFI17RUD ...
Страница 42: ...39 Outdoor Controller Set of For YN009GMFI22RPD YN012GMFI22RPD For YN018GMFI22RPD ...
Страница 44: ...41 RB009GMFILCFHD Code 0 Code 1 Code 2 Code 3 Code 4 ...
Страница 45: ...42 RB012GMFILCFHD Code 0 Code 1 Code 2 Code 3 Code 4 ...
Страница 46: ...43 RB018GMFILCFHD Code 0 Code 1 Code 2 Code 3 Code 4 ...
Страница 47: ...44 RB024GMFILCFHD Code 0 Code 1 Code 2 Code 3 Code 4 ...
Страница 48: ...45 RB036GMFILCFHD Code 0 Code 1 Code 2 Code 3 Code 4 ...
Страница 49: ...46 RB048GMFILCFHD Code 0 Code 1 Code 2 Code 3 Code 4 ...
Страница 58: ...55 12 Field Wiring 36 000 and 48 000 BTU Models ...
Страница 100: ...97 P U P V ...
Страница 101: ...98 P W P N ...
Страница 116: ...113 4 Remove the evaporator support board 5 Screw off the fixing screws to remove the evaporator 4 screws 1 screw ...